E32.0.05.6C-06
Manual for connection and operation of the GIR 2000 Pt
page 2 of 12
I N D E X
1. INTRODUCTION ........................................................................................................................................................ 2
2. SAFETY REGULATIONS .......................................................................................................................................... 3
3. ELECTRIC CONNECTION ....................................................................................................................................... 4
3.1. Terminal assignment ................................................................................................................................................ 4
3.2. Connection data ....................................................................................................................................................... 4
3.3. Connecting a Pt100-temperature probe.................................................................................................................... 4
3.4. Connecting switching output ................................................................................................................................... 5
4. INPUT-CONFIGURATION: SELECT FILTER VALUE ....................................................................................... 5
5. CONFIGURATION OF THE OUTPUT FUNCTIONS ............................................................................................ 6
5.1. Selection of the output function ............................................................................................................................... 6
5.2. 2-point-controller ..................................................................................................................................................... 6
5.3. Minimum/maximum-alarm ...................................................................................................................................... 7
6. SWITCHING POINTS AND ALARM-BOUNDARIES ........................................................................................... 8
6.1. Menu calling ............................................................................................................................................................ 8
6.2. 2-point-controller ..................................................................................................................................................... 9
6.3. Minimum/maximum-alarm ...................................................................................................................................... 9
7. OFFSET- AND SLOPE-ADJUSTMENT ................................................................................................................. 10
7.1. Menu calling and adjustment ................................................................................................................................. 10
8. MIN-/MAX-VALUE MEMORY:.............................................................................................................................. 11
9. ALARM DISPLAY ..................................................................................................................................................... 11
10. ERROR CODES ....................................................................................................................................................... 11
11. SPECIFICATION ..................................................................................................................................................... 12
12. DISPOSAL NOTES .................................................................................................................................................. 12
1. Introduction
The GIR 2000 Pt is a microprocessor controlled displaying
device.
The devices supports one input for the connection of:
- RTD (Pt100, 3-wire)
The device features additional one switching output, which can be configured as 2-point-controller or
min./max. alarm.
The state of the switching outputs (re
lays) is displayed with the LED “2”.
An upcoming alarm condition is displayed by LEDs “alarm”, “max” and “min”.
When leaving our factory the GIR 2000 Pt has been subjected to various inspection tests and is completely
calibrated.
Before the GIR 2000 Pt can
be used, it has to be configured for the customer’s appli-
cation.
Hint: By calling a configuration menu (configuration of the output function, offset- and slope-
adjustment) the measurement and regulation of the device will be deactivated.
By leaving the menu the device will be reinitialised and the measuring/regulation will be started
again.
ON/SP
SET
min.
OFF/Hy.
1
2
max.
ALARM
Scale
Analog
CAL
Scale
Analog
CAL
ON/SP
SET
min.
OFF/Hy.
1
2
max.
GIR/GIA
ALARM
SET
1
2
3
4