E24.0.13.6C-05
GIA 0420 WK - EX Connection and operating manual
page: 3 of 6
GREISINGER electronic GmbH Hans-Sachs-Straße 26 D-93128 Regenstauf Fax 0049-9402 9383-33
Technical Specification
Input signal:
4 ... 20 mA (2-wire)
max. allowed input current:
40 mA
Reverse voltage protection:
polarized installation
Voltage load:
approx. 3 V
Display:
10 mm high LCD-display
Display range:
starting and end value freely selectable
Maximum display value:
9999 digits
Minimum display value:
-1999 digits
Decimal point:
any position
Measuring accuracy:
0.2% ± 1 digit
Temperature drift:
100 ppm / °C
Measuring interval:
approx. 5 measurements / sec.
Filter:
3 stages can be switched on
Nominal temperature:
25 °C
Ambient temperature:
0 to 50 °C
Relative atmospheric humidity:
0 to 80 %RH (non condensing)
Electromagnetic compatibility:
In accordance with EN61326
additional error:
< 1%
(within the range of 140 - 170MHz: < 2.5%)
Ex protection:
II 2 G EEx ib IIC T4
according to EC-Type-Examination Certificate: ZELM 03 ATEX 0135
Housing:
ABS. Front screen made of polycarbonat.
48.5 x 48.5 x 35.5 mm (L x W x D)
Connection:
2-wire connection cable, lenght approx. 2 m,
no polarity
IP rating:
front side IP65
Fault codes
In case of unacceptable conditions in the system a fault code will be displayed.
Fault codes have been defined as follows:
FE 1: Measuring range has been exceeded
This fault code indicates that the measuring range of the A/D converter has been exceeded.
Potential fault cause:
transmitter damaged
short-circuit in transmitter connection
GIA0420WK not/incorrectly configurated
Remedies:
FE 1 will be reset as soon as the measuring values are back within their
permissible range. Please check your transmitter and transmitter
connecting cables.
FE 2: Measuring values have fallen below permissible range
This fault code indicates that the measuring values of the A/D converter have fallen below the
permissible range.
Potential fault cause:
transmitter damaged
transmitter connection interrupted
GIA0420WK not/incorrectly configurated
Remedies:
FE 2 will be reset as soon as the measuring values are back within their
permissible range. Please check your transmitter and transmitter
connecting cables.
FE 6: New Startup
This error message signals that the instrument is currently performing the startup sequence.
possible cause:
Input current to low
Remedies:
FE6 will be reset as soon as the instrument has finished its startup
sequence. Check the loop current.