MicroGuard 511 Retrofit
10
W450512 03/08
Reset Function Kick-Out
Reset function kick-out override is used to reposition the boom when the crane is being rigged. If the
boom is topped out, it is often necessary to put the boom in a position that could cause function kick-
out. Press and hold the
CanCel
key for approximately five seconds to reset the relay and another
beep will be heard confirming the override. The override condition will remain in effect only as long as
the
CanCel
key is held. When the
CanCel
key is released, the system will return to locked out mode
until the condition it is corrected. Should a different alarm condition occur while the relay is over-
ridden, the new alarm condition will cause the controls to disconnect again.
m
WARNING
WHEN THE RESET FUNCTION KICK-OUT OVERRIDE FUNCTION IS USED, THERE IS NO
PROTECTION FROM OVERLOAD OR TWO-BLOCK CONDITION.
Operator Settable Alarms
Accessing the Operator Alarms
Press the operator alarms button to access the
operator alarms. The information window will show
the current status of the alarms. The following
operator alarms are available:
Minimum Boom Angle
•
Maximum Boom Angle
•
Maximum Boom Length
•
Maximum Tip Height
•
Each button acts as a toggle switch turning the alarm on or off if the alarm is off, press the
appropriate push button to turn the alarm on. If the alarm is on, press the appropriate push button to
turn the alarm off.
Setting Minimum Boom Angle Alarm
Move the boom to the desired minimum angle. Press
the
operaTor alarm
key to access the operator
alarm screen. Press the key adjacent to “Min Angle”
to set to the current position.
If the angle of the boom falls below the minimum
angle set, the red warning light will flash and the
audible alarm will sound.
Press the key adjacent to “Min Angle” again to turn of
the minimum boom angle alarm.
TEST
SET
MAX
TEST
SET
MAX