GreenWorks 4101502 Owner'S Manual Download Page 8

14

15

W A R N I N G

Disconnect air compressor from power source and bleed off all air pressure before attempting 

any maintenance or repair.

SHUTDOWN AND STORAGE:

MAINTENANCE

1. Turn the switch to the OFF position

2. Turn the pressure regulator knob fully counterclockwise to close airflow from air outlet port.  

    Check the outlet pressure gauge to ensure that it reads 0 PSI.

3. Remove the air hose and any air accessories.

4. Drain moisture from the air tank by slowly opening the air tank drain valve by turning counter 

    clockwise. Tilt tank to remove all moisture. Once all the moisture has drained out, close the  

    fitting securely.

5. Allow the compressor to cool down.

6. Wipe the air compressor clean and store it in a clean, dry, and non-freezing location.

WHEN PERFORMING ANY MAINTENANCE OR SERVICE:

1. The air compressor must be turned off.

2. Open tank drain to bleed off all air pressure before attempting any maintenance or repair.

3. Allow compressor to fully cool before attempting any maintenance or repair.

Check the air compressor frequently for any visible problems and follow maintenance

procedures each time the compressor is used.

MAINTENANCE CHECKLIST:

Daily:

• Drain accumulated liquid from tank.

• Check for unusual noise and/or vibrations.

• Check that all fasteners are secure.

• Wipe compressor clean.

Monthly:

• Check for air leaks.

TROUbLESHOOTING

PROBLEM POSSIBLE CAUSES

LIKELY SOLUTIONS

C o m p r e s s o r 

does not start or 

restart

1. Tank(s) already pressurized.

2. Power cord not plugged in 

properly.

3. No power at outlet.

4. Thermal overload switch 

tripped.

5. building power supply circuit 

tripped or blown fuse.

6. Cord wire size is too small 

or cord is too long to properly 

power compressor.

7. Compressor needs service.

1. No problem. Compressor will start when needed.

2. Check that cord is plugged in securely.

3. Reset circuit breaker, or have outlet serviced by a qualified 

technician.

4. Turn off Compressor and wait for it to cool down.

Press reset button. Resume operation.

5. Reset circuit or replace fuse. Check for low voltage 

conditions. It may be necessary to disconnect other electrical 

appliances from the circuit or move the compressor to its 

own circuit.

6. Use larger diameter or shorter extension cord or eliminate 

extension cord. See Recommended Wire Gauge for 

Extension Cords in Safety section.

7. Have unit inspected by a qualified technician.

Compressor not

building enough

air pressure

1. Air filters need cleaning/

replacing.

2. Check Valve needs service.

3. Compressor not large enough 

for job.

4. Loose fittings.

5. Hose or hose connections too 

narrow.

6. High altitude reducing air 

output.

1. Check inlet and outlet filters. Clean and/or replace as 

needed.

2. Have technician clean or replace, as needed.

3. Check if accessory CFM is met by Compressor. If 

Compressor cannot supply enough air flow (CFM), you need 

a larger Compressor.

4. Reduce air pressure, then check all fittings with a 

soap solution for air leaks and tighten as needed. Do not 

overtighten.

5. Replace with wider hose and/or hose connections.

6. Higher altitudes require compressors with greater output.

Overheating

1. Unusually dusty environment.

2. Cord is too small of a 

gauge or too long to handle 

compressor.

3. Unit not on level surface.

1. Move unit to cleaner environment.

2. Increase cord size or use shorter length extension cord, or 

eliminate extension cord. See Recommended Wire Gauge 

for Extension Cords in Safety section.

3. Reposition unit on a level surface.

Compressor

starts and stops

excessively

1. Loose fittings.

2. Compressor not large enough 

for job.

1. Reduce air pressure, then check all fittings with a 

soap solution for air leaks and tighten as needed. Do not 

overtighten.

2. Check if accessory CFM is met by Compressor. If 

Compressor doesn’t reach accessory CFM, you need a 

larger Compressor.

Excessive noise

Loose fittings.

Reduce air pressure, then check all fittings with a soap 

solution for air leaks and tighten as needed. Do not 

overtighten.

Moisture in

discharge air

Too much moisture in air.

Install inline air filter/dryer, and/or relocate to less humid 

environment.

Safety Valve 

“pops”

Safety valve needs service.

Pull on test ring of safety valve. If it still pops, replace.

Air leaks from

pump or fittings

Loose fittings.

Reduce air pressure, then check all fittings with a soap 

solution for air leaks and tighten as needed. Do not 

overtighten.

Air leaks from 

tank

Defective or rusted tank.

Have tank replaced by a qualified technician.

Drain moisture from tank daily to prevent future corrosion.

Follow all safety precautions whenever diagnosing or servicing the compressor. Disconnect 

power supply before service.

Summary of Contents for 4101502

Page 1: ...GAL OIL FREE PANCAKE COMPRESSOR 4101502 Read all safety rules and instructions carefully before operating this tool Owner s Manual TOLL FREE HELPLINE 1 888 90WORKS 888 909 6757 www GreenWorksTools co...

Page 2: ...explain the levels of risk associated with this product DANGER Indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially h...

Page 3: ...e for breathing The air stream may contain carbon monoxide toxic vapors or solid particles from the air tank Breathing these contami nants can cause serious injury or death Exposure to chemicals in du...

Page 4: ...uently use the tire gauge to prevent over inflation 2 Never drill into weld or make any modifications to the air tank or its attachments Never attempt to repair a damaged or leaking air tank Replace w...

Page 5: ...an fall from a table workbench or roof causing damage to the compressor and could result in serious injury or death to the operator Become familiar with these terms before operating the unit CFM Cubic...

Page 6: ...body of the compressor 2 Firmly press fit the male quick connect portion on the air hose into the female quick connect and release female quick connect locking hose in place NOTE When connecting or di...

Page 7: ...ick connector P N 3790150 1A 1 Tire chuck P N 37903110 1 Inflation needle P N 37902110 1 Blow gun adaptor P N 37911110 1 Tapered nozzle P N 37904110 2 Male plug P N 37909110 1 plumber tape P N 3790111...

Page 8: ...extension cord or eliminate extension cord See Recommended Wire Gauge for Extension Cords in Safety section 7 Have unit inspected by a qualified technician Compressor not building enough air pressure...

Page 9: ...calling our toll free helpline at 1 888 909 6757 1 888 90WORKS Transportation Charges Transportation charges for the movement of any power equipment unit or attachment are the responsibility of the p...

Page 10: ...18 19 parts list parts list...

Page 11: ...20 NOTES TOLL FREE HELPLINE 1 888 90WORKS 888 909 6757 Rev 00 09 11 14 Printed in China on 100 Recycled Paper...

Reviews: