Observe appropriate safety precautions
if working on steps or ladders. Wear
eye protection when breaking out wall
or window materials etc.
●
Siting Notes:
Where an open-flued oil or gas- fuelled
appliance is installed in the kitchen,
extract ventilation can cause the
spillage of flue gases. Care must be
taken to ensure ventilation is reduced
as appropriate, as set out in the
building regulations. The guide to the
regulations suggests that the reduced
provision should be an extract rate
20 l/s (72 m
3
/h) maximum. Kitchens
with solid-fuel appliances should not
have extract fans fitted.
●
The fan should not be sited where
it would be subject to a direct source
of heat in excess of 40ºC.
●
When installing wall mounted fans,
ensure that there are no buried cables
or pipes in the way. It is recommended
that this fan is mounted 1.8m above
floor level.
●
A clearance of 75mm to be allowed
on at least one side of the fan for
the removal of the internal grille.
●
Cleaning Notes:
Always isolate from the mains before
cleaning. Do not use solvents to clean
the fan. Wipe the front grille clean
using a damp cloth avoiding getting
any water into the internal fan unit.
READ ALL INSTRUCTIONS BEFORE COMMENCING INSTALLATIONS
Remove one piece Internal Grille using
screwdriver. Push in to free catch then
twist to remove grille.
Cut the duct to width of the plasterboard or
tiled wall with slight fall to exterior.
(Make provisions for cable).
Using No 8 screws, secure fan body to
ducting first making sure back draught
shutter is fitted, if required, and electrical
cable passes through as appropriate. Wire
fan (See wiring details).
WALL MOUNTING
(Using ED wall duct and EG external grille. 100mm and 150mm only)
1
4
Replace internal grille ensuring no wires
are trapped.
5
Screw the protective wall grille over the
external duct opening.
6
A
Ø
A
2
AXS100 Ø = 125 mm
AXSK/U/150 Ø = 180 mm
Fill in any gaps with mortar or foam and
make good internal and external walls.
Make sure that ducting remains circular
and screw holes are horizontal.
3
CEILING MOUNTING
Remove one piece Internal Grille using
screwdriver. Push in to free catch then
twist to remove grille.
Cut an opening through the ceiling for the
fan and electrical cable.
Place flexible ducting over the spigot of the
fan.
1
4
Fit ducting to spigot using ties supplied,
making sure impeller rotates freely.
Maximum duct length to comply with
Building Regulations:
AXS100:
3m
AXSU:
12m
AXSK/150:
Wall mounting only
5
8
X
Ø 12 for cable
X = 67mm for AXS100
X = 90mm for AXSU
Ø = 105mm for AXS100
Ø = 155mm for AXSU
Ø
2
Secure to ceiling using suitable screws first
making sure backdraught shutters are
removed but shutter spider is left in
position. Wire fan (See wiring details).
3
9
6
Detach the cord from the pcb by pulling
the cord through the pull cord’s link.
Installation Instructions for Axial Fans
for Bathroom, Toilets, Utility Rooms and Kitchens
AXS100, AXS100SELV, AXS125, AXSU, AXS150 & AXSK
Replace internal grille ensuring no wires
are trapped.
7