Intelligent Radar Level

 

Transmitter

   

Programming Menu

-

RD2690, RD6850 series

 

 

 

Greentech, Korea 

 

www.greentechkor.com                                                                                                                                                    E-mail: [email protected] 

 
When you want to edit the false ECHO GRAPH, press button SELECTION 
to move the arrow to the needed item and then press button OK for 
confirmation. This function can edit or modify the created false echo to 
adapt the request of special working conditions. After entering the false 
echo edition, LCD indicates as follows: 
(Note: this menu needs professional person for operation):   

FALSE ECHO EDITION 
START POINT   

   

    1.00          AMPLITUDE          1300m(d)   

END POINT                2.00          AMPLITUDE     

 

  1500m(d) 

Two points can be edited a time, the start point and the end point are the 
coordinates for the curve which is needed to be edited. The following 
corresponding value of amplitude is the value to be edited (Note: when 
input or alter the distance coordinates, the corresponding amplitude will 
automatically be updated according to the currently saved value which will 
act as reference for amplitude modification).   
 
When the modification for the two pairs of coordinates is finished, press 
button OK for confirmation of the modification. The instrument will 
automatically link the two points and create a new false ECHO GRAPH, 
substitute for the old curve. Press button OK for confirmation, LCD will 
indicate the false ECHO GRAPH after the modification this time for 
reference.   
And then press button ESC, LCD goes back to the edition interface for 
further edition. When the false echo edition reach to the request of the 
working conditions, press button ESC again, LCD exits false echo edition 
menu. Then LCD indicates as follows: 

FALSE ECHO EDITION   
SAVE IT? 

Press button OK for saving for what have been modified above. Press 
button ESC for giving up the current modification. 
 
 

 

4.2. Output mode:

 

This setting is for setting current output mode. When LCD indicates the 
menu number 4.1, press button SELECTION, LCD indicates as follows: 

CURRENT OUTPUT 
OUTPUT MODE: 4-20mA   
FAULT MODE:    NO CHANGE   
MINIMUM CURRENT: 4mA 

When LCD indicates current output mode for selection of 4-20mA or 20-
4mA, 4-20mA means that low medium level corresponds to 4mA, high 
medium level corresponds to 20mA: 20-4mA means that low medium level 
corresponds to 20mA, high medium level corresponds to 4mA.   
When LCD indicates current output selection menu 4.2, press button 
SELECTION to move the arrow to the output mode and press button OK 
for confirmation, then LCD indicates as follows: 

OUTPUT MODE                                            4.2 
NO CHANGE 
20.5mA 
22.0mA 
4.0mA 

Press button SELECTION to select the setting you need, press button OK 
for confirmation. 
Minimum current is used for se

lecting the minimum current as “4mA” or 

“3.8mA”. When LCD indicates current output selection menu 4.2, press 
button SELECTION to move the arrow to “minimum current”, and then 
press button OK for confirmation. LCD indicates as follows: 

Summary of Contents for RD2690 Series

Page 1: ...Selecting digits of edited parameters Indicating the content of the selected parameter Note hereinafter the button is called as KEY SELECTION for easy understanding Amending values of parameters Sele...

Page 2: ...button to enter programming state display programming main menu Each parameter editor to finish with OK button confirmation otherwise the editor is invalid When done editing press the Esc key to exit...

Page 3: ...ment High position adjustment is for measuring range setting It determines the proportion of output current linearity corresponding relationship together with low position adjustment When LCD indicate...

Page 4: ...ST WAVE AMPLITUDE DEFAULT WEAKEN THE FIRST WAVE AMPLITUDE WEAKEN 10dB LITTLE STRONGER THE FIRST WAVE STRENGTHEN 10dB STRONGER THE FIRST WAVE STRENGTHEN 20dB STRONGEST THE FIRST WAVE STRENGTHEN 40db 1...

Page 5: ...liquid DK adjustment menu LCD indicates as follows DK VALUE SMALL 1 3 5 YES NO Press button SELECTION to select YES and set the measurement when DK value is small LCD indicates as follow then input a...

Page 6: ...easurement result 1 4 Damping time Damping time When LCD indicates the menu number 1 3 press button SELECTION enter damping time setting menu LCD indicates as follows DAMPING TIME 1 4 6S Press button...

Page 7: ...be set When LCD indicates the menu number 1 7 press button SELECTION to enter measuring range setting menu LCD indicates as follows MEASURING RANGE SETTING 1 8 00 000m d Press button OK the correspond...

Page 8: ...er editing press button ESC exit indication programming and go back to the previous menu 2 2 LCD contrast adjustment When LCD indicates the menu number 2 1 press button SELECTION to enter LCD contrast...

Page 9: ...tes graph press button OK to enter curve zoom editing menu LCD indicates as follows CURVE ZOOM 3 4 ZOOM ALONG AXIS X ZOOM ALONG AXIX Y NO ZOOM Press button SELECTION to move the arrow for selecting zo...

Page 10: ...use the function of false echo setting to overcome its interference When LCD indicates the main menu and the menu number is 4 press button OK to enter service submenu LCD indicates as follows FALSE EC...

Page 11: ...e ECHO GRAPH after the modification this time for reference And then press button ESC LCD goes back to the edition interface for further edition When the false echo edition reach to the request of the...

Page 12: ...tting according to the needs 4 4 Measuring unit There are two choices of measuring units for users one is the metric system the other is imperial system When LCD indicates menu number 4 3 press button...

Page 13: ...n SELECTION to select the menu you need and press button OK for confirmation and perform the function 4 8 Password Password is used for the safety of the parameters Once the function is actuated you h...

Page 14: ...pper corner of the screen 3 Press button OK for confirmation Enter the diagnosis submenu 3 1 for indicating measurement peak minimum distance and maximum distance 4 Press button SELECTION to next prog...

Page 15: ...15 Intelligent Radar Level Transmitter Programming Menu RD2690 RD6850 series Greentech Korea www greentechkor com E mail info greentechkor com Attached Diagram...

Page 16: ...16 Intelligent Radar Level Transmitter Programming Menu RD2690 RD6850 series Greentech Korea www greentechkor com E mail info greentechkor com...

Reviews: