When
,
DAR,
or
PI
is
activated, pressing the
TEST
button will start the test. The LCD displays the
measurement along with a timer showing the remaining time in the test. The test automatically ends
when the timer reaches 0.
The following parameters indicate acceptable insulation:
DAR > 1.25
PI > 2
Backlight
Press
j
to turn on the backlight. Press again to turn off the backlight.
Note: The backlight will automatically shut off after 1 minute.
Standy Mode
To extend battery life, the megohmmeter will automatically switch to standby mode after approximately
5 minutes of inactivity. To restore normal operation, press any button or rotate the selector.
Using the Features