Greenheck Sure-Aire 386719 Installation, Operation And Maintenance Manual Download Page 2

Sure-Aire™ Flow Monitoring System

2

®

This instruction manual provides installation, operating, maintenance, and other information for the Sure-Aire™ 
electronics.

Receiving

Upon receiving the electronics, check to ensure all items are accounted for by referencing the packing list. Inspect 
each crate or carton for shipping damage before accepting delivery. Alert the carrier of any damage detected. The 
customer will make notification of damage (or shortage of items) on the packing list and all copies of the bill of lading 
which is countersigned by the delivering carrier. If damaged, immediately contact your local sales representative. 
Any physical damage to the unit after acceptance is not the responsibility of the manufacturer.

Unpacking

Verify that all required parts and the correct quantity of each item have been received. If any items are missing, 
report shortages to your local representative to arrange for obtaining missing parts. 

Storage

Electronics are protected against damage during shipment. If the electronics cannot be installed and operated 
immediately, precautions need to be taken to prevent deterioration during storage. The user assumes responsibility 
of the electronics and any accessories while in storage. The manufacturer will not be responsible for damage during 
storage. These suggestions are provided solely as a convenience to the user.
The ideal environment for the storage of electronics is indoors, above grade, in a low humidity atmosphere which 
is sealed to prevent the entry of blowing dust, rain or snow. Temperatures should be evenly maintained between 
30

°

 to 110

°

F (

-1° to 43°C

). Wide temperature swings may cause condensation and “sweating” of metal parts. All 

accessories must be stored indoors in a clean, dry atmosphere.

Removing from Storage

As electronics are removed from storage to be installed in their final location, they should be protected and 
maintained in a similar fashion until the control goes into operation. Environmental Operation Range: -4

°

 to 140

°

(

-20° to 60°C

).

1.    Mount the electronics in the vertical plane using 

four (4) #8-32 screws, field supplied. Open the front 
cover by unscrewing the two captive thumb screws 
to gain access to the four mounting locations.

    

Note:

  Mount the Sure-Aire™ electronics within 

75 feet of the fan.

WARNING

When wiring the electronics, you must follow industry 
standard practices for controls and protect against 
electrostatic discharge (ESD). Failure to exercise good 
ESD practices may cause damage to the electronics.

General Information

Installation

4-5/32 in.

(105.6 mm)

5-3/8 in.

(136.5 mm)

3-9/32 in.

(83.3 mm)

5 in.

(127 mm)

2.    Use 1/4-inch nylon tubing to connect the 

corresponding High (H) and Low (L), 1/4-inch 
quick connect, pressure ports of the Sure-Aire™ 
electronics to the high and low pressure ports on the 
fan.

3.  

Connect supply power:

 

Two input power options are available: 24 VAC / DC 
or 100-240 VAC. The wiring for each can be seen 
on page 4. For liquid tight applications, use only 
1/2-inch liquid tight conduit.

Power connection

High (H)

Low (L)

Wiring connection

Summary of Contents for Sure-Aire 386719

Page 1: ...P Modbus Temperature compensation for air density Tools Required Four 4 8 32 screws 1 4 inch nylon tubing length dependent on distance between fan and Sure Aire electronics maximum 75 feet 23 m each line Sensor wiring for temperature sensor if temperature sensor is being used Pressure ranges reflect differential pressures between the fan inlet and inlet cone not system static pressure Flow Accurac...

Page 2: ...ronics is indoors above grade in a low humidity atmosphere which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly maintained between 30 to 110 F 1 to 43 C Wide temperature swings may cause condensation and sweating of metal parts All accessories must be stored indoors in a clean dry atmosphere Removing from Storage As electronics are removed from storage to...

Page 3: ...ctronics page 7 Switch SW1 2 Wire 4 Wire Select Left Position 2 Wire Right Position 4 Wire 4 3 Temperature Density Compensation Temperature compensation can adjust airflow calculation based on changing airstream temperatures If temperature compensation is not used the air density value will be a function of standard air 70 F 21 C The supplied sensor measures the exterior temperature of the ductwor...

Page 4: ...er you are in i e Setup will change to Home and Home will change to Edit Home Screen To view the different settings use the Up and Down buttons to scroll through the list To adjust settings press Setup and scroll through the settings Below is information on the adjustable settings Settings Menu Home Screen Top Bottom View Press Edit to change Main Display Value Press Prev or Next to adjust what re...

Page 5: ... Server Device Settings Setting Value Baud Rate Set to match BMS Parity No Parity 1 Stop Bit APDU Timeout ms 1000 Number of APDU Retries 3 Max Master Address 127 Max Info Frames 1 Modbus RTU Slave When the electronics is configured for Modbus it will expose a total of seven 7 registers on the network The Modbus RTU Slave settings and list of registers can be seen below Modbus RTU Slave Device Sett...

Page 6: ...c fan model and size ΔP is the measured differential pressure across the inlet cone in wg and is the density of air lb ft3 CFM K P Voltage and Amperage Signal If using the analog signal linear to flow the max flow is automatically calculated based on the pressure range and K factor input into the electronics The max value is displayed in the setup menu If output signal is linear to pressure the co...

Page 7: ...f calibrating using 4 20 mA a series load resistor between 200 and 900 ohms is required 5 Set multimeter to the correct measurement units VDC or mA 6 Apply power to the Sure Aire electronics 7 Press the Setup button on the LCD panel 8 Verify the analog signal is setup for your measurement and that the signal is linear to Differential Pressure 9 Go to the Trans Min Trans Max screen Record the value...

Page 8: ...79 not applicable not applicable 355 329 8 not applicable not applicable 179 not applicable 179 not applicable not applicable 400 406 9 not applicable not applicable 179 408 179 248 not applicable 450 536 10 not applicable not applicable 179 not applicable 179 202 not applicable 500 652 12 355 592 244 408 244 296 not applicable 560 847 13 not applicable 701 not applicable not applicable 296 351 no...

Reviews: