Damper Sizing Information

Specifications

Copyright © 2008 Greenheck Fan Corporation

SEFSD-211 Rev. 5 March 2008

Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size. 

The following figures show maximum damper section size and assembly configurations for multi-section dampers.

Single Section

30”

24”

30”

24”

48”

Multi Section

Transitioned Damper 

Dimensions

When a fire/smoke damper is being used in conjunction with round or oval ductwork, the 

SEFSD-211 can be supplied in a factory sleeve with round or oval transitions on both ends 

of the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show 

overall damper size.

These dimensions are furnished approximately 

1

/

4

 in. 

(6mm) undersize, except round and oval dimensions which 

are approximately 

1

/

8

 in. (3mm) undersize.

Ts = (2)(Sleeve Thickness)

D*  +  2 in. (51mm) +T  s 

D* 

TYPE  R 

 

16 in. (406mm) 

Min. 

8

 in. 

D*  +  2 in. (51mm)+T  s 

TYPE  O 

H* 

W* 

  

+  2 in. (51mm)+T s 

H*  +  2 in. (51mm)+T s 

W* 

H* 

TYPE  C 

  

H*  +  2 in. (51mm)+T s 

 

(54mm)

16 in. (406mm) 

Min. 

/

8

 in.

(54mm)

16 in. (406mm) 

Min. 

W* +  2 in. (51mm)+T s 

(54mm)

8

 in.

Combination Fire Smoke Dampers meeting the following specifications 

shall  be  furnished  and  installed  where  shown  on  plans  and/or  as 

described in schedules. Dampers shall meet the requirements of the 

latest edition of NFPA 80, 90A, 92A, 92B, 101, & 105 and further shall 

be tested in accordance with the latest edition of UL Standards 555 

and 555S. Dampers shall have a UL 555 fire rating of 1½ hours and be 

of low leakage design qualified to UL555S leakage class I.

Each damper /actuator combination shall have a UL555S elevated 

temperature rating of 250°F (121°C) minimum and shall be operational 

and dynamic rated to operate at maximum design air flow at its 

installed location. Each damper shall be supplied with an appropriate 

actuator installed by the damper manufacturer at the time of damper 

fabrication. Damper actuator shall be (specifier select one of the 

following) electric type for 120 (24 or 230) volt operation 

or

 pneumatic 

type for 25 psi minimum (30 psi maximum) operation.

The  Damper  Manufacturers  submittal  data  shall  certify  all  air 

performance  pressure  drop  data  is  licensed  in  accordance  with  the 

AMCA  Certified  Ratings  Program  for  Test  Figures  5.2,  5.3  and  5.5.  

Damper air performance data shall be developed in accordance with 

the latest edition of AMCA Standard 500-D. Dampers shall be labeled 

with the AMCA Air Performance Seal.

Damper  blades  shall  be  16  ga.  (1.5mm)  316  stainless  steel  3V  type 

with  three  longitudinal  grooves  for  reinforcement.  Blades  shall  be 

completely  symmetrical  relative  to  their  axle  pivot  point,  presenting 

identical resistance to airflow and operation in either direction through 

the damper (blades that are non-symmetrical relative to their axle pivot 

point or utilize blade stops larger than 1/2 in. [13mm] are unacceptable). 

Damper frames shall be 316 stainless steel formed into a structural hat 

channel shape with reinforced corners. Bearings shall be 316 stainless 

sleeve type rotating in extruded holes in the damper frame. Jamb seals 

shall be stainless steel compression type.

All  UL  555  and  555S  Dynamic  Closure  Ratings,  Operational  Ratings 

and  Leakage  Ratings  shall  be  qualified  for  airflow  and  pressure  in 

either direction through the damper. UL ratings shall allow for mounting 

damper vertically (with blades running horizontal) or horizontally. 

Basis of design is Greenheck Model SEFSD-211.

Summary of Contents for Stainless Steel 3V Blades SEFSD-211

Page 1: ...eel jamb seals Linkage 316 stainless steel concealed in jamb Axles 1 2 in 13mm diameter 316 stainless steel Bearings 316 stainless steel sleeve type Closure Device 165º F 74ºC RRL Size Limitations Minimum Size 8 in W x 6 in H 203mm W x 152mm H Maximum Size Single Section 24 in W x 30 in H Horizontal or Vertical Mount 610mm W x 762mm H or 22 in W x 36 in H Vertical Mount 559mm x 914mm Multiple Sect...

Page 2: ...ystem AMCA Test Figures Figure 5 3 Illustrates a fully ducted damper This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper Figure 5 2 Illustrates a ducted damper exhausting air into an open area This configuration has a lower pressure drop than Figure 5 5 because en...

Page 3: ...ssureDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg 500 0 04 500 0 02 500 0 01 500 0 01 1000 0 14 1000 0 07 1000 0 04 1000 0 06 1500 0 31 1500 0 16 1500 0 09 1500 0 13 2000 0 55 2000 0 29 2000 0 16 2000 0 23 2500 0 86 2500 0 45 2500 0 25 2500 0 36 3000 1 24 3000 0 65 3000 0 36 3000 0 52 3500 1 69 3500 0 89 3500 0 49 3500 0 70 4000 2 20 40...

Page 4: ...00 0 48 3500 0 33 3500 0 53 4000 1 44 4000 0 63 4000 0 42 4000 0 70 12in x12in 305mm x 305mm 24in x24in 610mm x 610mm 36in x36in 914mm x 914mm 12in x48in 305mm x 1219mm Velocity fpm Pressure Drop in wg 500 0 02 1000 0 07 1500 0 16 2000 0 29 2500 0 45 3000 0 64 3500 0 88 4000 1 14 48 in x 12 in 1219mm x 305mm R Greenheck Fan Corporation certifies that the model SEFSD 211 shown herein is licensed to...

Page 5: ...fpm PressureDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg 500 0 06 500 0 03 500 0 03 500 0 03 1000 0 22 1000 0 14 1000 0 12 1000 0 13 1500 0 50 1500 0 31 1500 0 26 1500 0 30 2000 0 89 2000 0 54 2000 0 46 2000 0 53 2500 1 39 2500 0 85 2500 0 73 2500 0 83 3000 2 00 3000 1 22 3000 1 05 3000 1 19 3500 2 72 3500 1 66 3500 1 42 3500 1 62 4000 3 55 4000 2 17 4000 1 86 4000 2 ...

Page 6: ...OR 12 305 12 305 Actuators and Accessories Space Envelopes Externally mounted actuators always require space out side of the damper sleeve The S dimension illustrates the clearance required for various available actuators On dampers less than 18 in 457mm high actuators may also require clearances above and or below the sleeve B and T dimensions are worst case clearance require ments for some dampe...

Page 7: ...perature rating of 250 F 121 C minimum and shall be operational and dynamic rated to operate at maximum design air flow at its installed location Each damper shall be supplied with an appropriate actuator installed by the damper manufacturer at the time of damper fabrication Damper actuator shall be specifier select one of the following electric type for 120 24 or 230 volt operation or pneumatic t...

Reviews: