background image

Copyright © 2009 Greenheck Fan Corporation

Double Flange SMD

Rev. 1 June 2009

Item 

Description

1. 

Damper frame

2.  

Duct outlet

3.  

Fan (not limited to centrifugal)

4.  

#10 sheet metal screws

5. 

Actuator

The actuators are to be installed to function per system 
requirements and to be controlled by smoke detection 
devices. 

1

4

2

3

5

fan iSolation application

     For air handling equipment isolation, leakage rated dampers are designed to operate with blades running horizon-

tally. Dampers can be installed in a vertical or horizontal position. Sealants and damper seal materials meet the 
requirements of NFPA90A for smoke developed rating (<50) and flame spread index (<25) as tested per UL723/
ASTME84-91A/NFPA 255. Dampers can be attached to the fan system discharge or inlet without being 24 in. 
(610mm) of a smoke barrier when used as an air handling equipment isolation damper.