background image

3. DUCT TO SLEEVE CONNECTIONS

   Dampers are supplied with sleeves and actuators from 

the factory and can be installed without the need for 
additional field installed sleeves.

   Gauge of factory furnished sleeve determines the type 

of duct to sleeve connections required (see table below). 
Any duct connection other than those breakaway 
connections described on page 6 are considered rigid. 
Factory furnished duct collars, type R and O, are also 
considered breakaway (see 

Fig. 2

).

 

Sleeve Gauge

Duct Dimension

Type of Duct 

to Sleeve 

Connection 

Permitted

14 ga. (0.075 in.) 

- 10 ga. (0.138 

in.)

[2mm - 3.5mm]

All duct sizes

Rigid or 

Breakaway

16 ga. (0.060 in.)

[1.5mm]

36 in. (914mm) max. width
24 in. (610mm) max. width

24 in. (610mm) diameter

Rigid only

16 ga. (0.060 in.)

[1.5mm]

All duct sizes

Breakaway only

18 ga. (0.048 in.)

[1.2mm]

85 in. (2159mm) wide and 

over

20 ga. (0.036 in.)

[0.9mm]

55 in. - 84 in. wide

(1397mm - 2134mm)

22 ga. (.030 in.)

[0.76mm]

31 in. - 54 in. wide

(787mm - 1372mm)

24 ga. (0.024)

[0.6mm]

13 in. - 30 in. wide
(330mm - 762mm)

26 ga. (0.018 in.)

[0.46mm]

12 in. wide and under

(305mm)

See page 6 for additional information on breakaway sleeve connections.
Sleeve thickness must not be less than the gauge of the connecting duct.
UL Standard 555 requires all ducts to terminate at fire damper sleeves.

4.  SECURING THE DAMPER/SLEEVE ASSEMBLY TO 

WALL OPENINGS

   Damper/sleeve assemblies must be installed in wall 

openings using retaining angles on at least one side of 
the wall as described below:

  •  Retaining angle must be a minimum of 16 gauge 

(1.5mm) steel and have a minimum of 1 

1

/

2

 in. x 1 

1

/

2

 in. 

(38mm x 38mm) legs.

  •  Retaining angle must be attached to the damper using 

one or more of the following methods of attachment 
(refer to label on outside of sleeve for ‘No Screw’ 
area):

 

• Tack or spot welds

 

• #10 (

3

/

4

 in. max. [19mm]) sheet metal screws

 

• 

1

/

4

 in. (6mm) bolts and nuts

 

• 

3

/

16

 in. (5mm) steel pop rivets

   A minimum of two connections per side, top, and 

bottom, 12 in. (305mm) O.C. maximum for openings of 
48 in. W x 32 in. H (1219mm x 812mm) and less, and 
6 in. (152mm) O.C. for openings 100 in. W x 32 in. H 
(2540mm x 32mm) or less. The angles must be attached 
to all 4 sides of the sleeve with butt joints at each 
corner. A minimum of two attachments are required 
on each side, top and bottom. Ensure that attachment 
device does not interfere with the operation of the 
damper and the free movement of the damper blades. 
The angles need not be attached to each other at the 
corners. Do not secure the retaining angle to the fire 
separation (see 

Fig. 3

).

  •  Retaining angles must completely cover the 

clearance space between the damper and the wall 
opening, plus overlap the wall a minimum of 1 in. This 
coverage includes all corners.

  •  Retaining angles should not be fastened to the wall 

material. The angles should only sandwich the wall 
and allow for damper expansion during periods of 
intense heat.

Damper 

Model

Maximum Single 

Section Size

Maximum Multiple 

Section Size

FSD-311V

50 x 32

100 x 32

Type R and O

Factory Furnished

Duct Collars Qualify

As Breakaway

Connections

Duct

Damper

Sleeve

Wall or Floor

Type C, O, R

Fig. 2

Damper with type R or O transition factory 

furnished.

2 in. 

Max.

6 in. 

Max.

Sleeve

Retaining

Angle

Damper

Duct

Min. 1 in.

Overlap*

Wall or

Floor

Retaining

Angle

*only applicable for damper sizes above 36 in. x 36 in.

6 in. 

Max.

2 in. 

Max.

Both vertical and horizontal damper installations are 
typified by these drawings.

Fig. 3

4

Summary of Contents for FSD-3XXV Series

Page 1: ...dance with combination fire smoke damper requirements established by National Fire Protection Association NFPA Standards 80 90A 92A 92B 101 105 BOCA National Building Codes ICBO Uniform Building Codes IBC International Building Codes SBCCI Standard Building Codes New York City MEA listing 260 91 M California State Fire Marshal Listing 3225 0981 103 and 3230 0981 104 Receiving and Handling Upon rec...

Page 2: ...e installed into duct or opening square and free of twist or other misalignment Damper must not be squeezed or stretched into duct or opening Out of square racked twisted or misaligned installations can cause excessive leakage and or torque requirements to exceed damper actuator design 6 Damper and actuator must be kept clean and protected from dirt dust and other foreign materials prior to and af...

Page 3: ...l floor openings are Galvanized steel fire dampers and sleeves 1 8 in 3mm per foot of damper width and height with a minimum clearance of 1 4 in 6mm maximum of 1 1 2 in 38mm Recommended clearances for width and or height dimensions of 1 36 in 914mm or less 1 2 in 13mm clearance These are total clearances ignoring fastener heads and do not need to be equally spaced around the damper 2 SLEEVE LENGTH...

Page 4: ... be attached to the damper using one or more of the following methods of attachment refer to label on outside of sleeve for No Screw area Tack or spot welds 10 3 4 in max 19mm sheet metal screws 1 4 in 6mm bolts and nuts 3 16 in 5mm steel pop rivets A minimum of two connections per side top and bottom 12 in 305mm O C maximum for openings of 48 in W x 32 in H 1219mm x 812mm and less and 6 in 152mm ...

Page 5: ...he TOR thermostats and indicator switches If either the TOR or the RRL is ordered with a pneumatic actuator an EP switch is required with an appropriate electric power circuit to allow the electric thermostat to control the pneumatic actuator PRV The PRV pneumatic relief valve option is heat responsive device used with pneumatic actuators This can be used in place of EP switch where a RRL is used ...

Page 6: ...each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket Transverse joints illustrated can be applied as top and bottom joints with Drive Slip side joints in duct heights up to 20 inches 508mm see Fig 10 Round and Oval Duct Breakaway Connections Round or flat oval ducts connected to Type R or O damper collars shall be attached with 10 19mm ...

Page 7: ...ls do not use oil based lubricants or any other lubricants that attract contaminants such as dust Dampers and their actuator s must be maintained cycled and tested a minimum in accordance with The latest editions of NFPA 80 90A 92A 92B 101 105 UL864 AMCA 503 03 and local codes Actuator manufacturer recommendations Damper Troubleshooting The following is a possible cause and correction list for com...

Reviews: