background image

Specifications

Backdraft dampers meeting the following specifications 
shall be furnished and installed where shown on plans and/
or as described in schedules. Dampers shall consist of: 
6063T5 extruded aluminum channel frame (0.063 in. [1.6mm] 
thick) with 2 in. (51mm) depth; blades from 0.050 in. (1.3mm) 
6063T5 extruded aluminum; synthetic polycarbonate axle 

bearings; damper shall be equipped with extruded vinyl blade 

seals; and internal 

1

/

8

 in. (3mm) aluminum linkage. Damper 

1.0

.9

.8
.7
.6

.5

.4

.3

.2

15
10

9

8
7
6

5

4

3

2

Air Leakage in CFM/Sq. Ft.

1          

 2         3     4     

  5   6   7  

  8  9 10

 20         30     40     

 

50  60  

 

70  

 

80 

 

90

 

100     150

ES

Static Pressure Difference (in. wg)

Leakage testing was conducted in accordance with AMCA 
Standard 500-D and is expressed as CFM per sq. ft. of 
damper face area. All data has been corrected to represent 

standard air at 0.075 lb/ft

(1.201 kg/m

3

).

Leakage

36” x 36” Damper

   

 

                      ÆP  in. wg   Velocity

               

Operational Data

                           

(Pa)      fpm (m/s)

 

Without Weights

       Blades Start to Open      0.05 (12)              35 (.18)

 

                     Blades Fully Open           0.27 (67) 

1000 (5.1)

 

With Weights

          Blades Start to Open    0.015 (3.7) 

   15 (.08)

 

                     Blades Fully Open           0.13 (32) 

  600 (3.1)

Velocity (fpm)

1

x 10

Pr

essur

e Loss ( 

In. w

.g.)

10

9

8

7
6
5

4

3

2

  2          3      4      5   6   7    8  9 10

1.0

.9

.8

.7
.6
.5

.4

.3

.2

.10

.09

.08

.07
.06
.05

.04

.03

.02

x 100

  2          3      4      5   6   7    8  9 10

x 1000

  2          3      4      5   6   7    8  9 10

 

With 

We

igh

ts

Wit

hout

 Wei

ghts

Pressure Drop

36” x 36” Damper

manufacturer’s printed application and performance data 
including pressure, velocity and temperature limitations 
shall be submitted for approval showing damper suitable 
for pressures to 2.5 in. wg (623 Pa), velocities to 2000 fpm 
(10.2m/s) and temperatures to 180°F (82ºC). Testing and 

ratings to be in accordance with AMCA Standard 500-D. 

Basis of design is Greenheck model ES-30.

Performance data results from testing a 36” x  36” damper 

in accordance with AMCA Standard 500-D using Figure 
5.5 (no duct either side). All data has been corrected to 

represent standard air at 0.075 lb/ft

(1.201 kg/m

3

).

Leakage

Pressure Drop

Copyright © 2008 Greenheck Fan Corporation

ES-30 Rev. 3 Aug 2008

Performance Data                                              ES-30

Reviews: