background image

IN THIS GROOVE.

RETAINER PLATE

DO NOT PLACE

IN THIS GROOVE.

DO NOT PLACE
RETAINER PLATE

DAMPER FRAME

DAMPER FRAME

WOOD
STUD

MIN

1.00

STUD

METAL

1.00
MIN

3

Installation - 

Continued

2. sleeVe leNGtH aND Wall/FlooR 

tHICKNess

  Insert the damper assembly into the prepared opening, 

to appropriate depth (see page 2, 

Fig. 1

).

  Recommended maximum and minimum insertion depth 

can be exceeded as long as the  CL of the damper 

blade remains within the plane of the wall/floor. 

 

IMPoRtaNt saFety DaNGeR!

 To avoid causing 

death or serious bodily harm to building occupants, do 
not insert screws into the damper frame unless used 
for duct connection within 2 in. (51mm) of the frame 
end.

  The sleeve may extend a maximum of 6 in. (152mm) 

beyond both sides of the wall or floor. Recommended 
standard sleeve lengths for various wall/floor 
thicknesses are:

3. DUCt to sleeVe CoNNeCtIoNs

  Dampers are supplied with sleeves from the factory 

and can be installed without the need for additional 
field installed sleeves.

  Gauge of factory furnished sleeve determines the 

type of duct to sleeve connections required (see table 
below). Any duct connection other than the breakaway 
connections are considered rigid. 

O 2 in.  Min.

Wall/Floor Opening

= Nominal Size + 7/8 in. Min.

1.00 in. Typ.

Fasteners

Clamping

Screw

Nut

Retaining

Plate Assembly

Clamping Screw

Fig. 2

5. Recommended Preparation of openings in 

Wood and Metal stud Walls

•  Frame wall openings as shown below. (see 

Fig. 3

)

•  Double vertical studs are not required for openings   

36 in. x 36 in. (914mm x 914mm) or smaller.

•  Gypsum wall board must be fastened 12 in. (305mm) 

on center to all stud and runner flanges surrounding 
opening. (see 

Fig. 4

)

•  All construction and fasteners must meet the 

requirements of the appropriate wall design (See UL 
Fire Resistance Directory) and/or local codes.

Fig. 3

4. seCURING tHe DaMPeR/sleeVe asseMBly 

to Wall aND FlooR oPeNINGs

  Damper assemblies must be installed in wall/floor 

openings using a single retaining plate on either side 
of the wall/floor or by using a retaining plate on both 
sides of the wall/floor. The use of a second retaining 
plate is allowed, but is not necessary. A single retaining 
plate is provided with the dampers. A second retaining 
plate can be ordered as an option.

  •  The retaining plate(s) will open up for easy installation 

when the clamping screw is loosened. If necessary, 
remove the clamping screw and nut (see 

Fig. 2

).

     (IMPORTANT: The clamping mechanism should 

face away from the wall/floor).

 Retainer plate(s) are 

designed to mount flush to the wall/floor and hold the 
damper in the wall/floor opening.

O 2 in.  Min.

Wall/Floor Opening

= Nominal Size + 7/8 in. Min.

1.00 in. Typ.

Fasteners

Clamping

Screw

Nut

Retaining

Plate Assembly

Clamping Screw

Wall/Floor Thickness 

Dimension (T

w

)

Inches (mm)

Sleeve Length

Dimension (L)

Inches (mm)

Up to 61/2 (165)

13 5/8 (346)

61/2 - 81/2 (165 - 216)

15 5/8 (397)

81/2 - 101/2 (216 - 267)

17 5/8 (448)

Sleeve Gauge

(mm)

Duct Dimension

Maximum

Inches (mm)

Type of Duct to 

Sleeve Connection 

Permitted

10 ga. (3.5)

24 (610) 

Rigid or Breakaway

14 ga. (2)

16 ga. (1.5)

20 ga. (1mm)

24 (610)

Breakaway only

Sleeve thickness must not be less than the gauge of the 
connecting duct.
UL Standard 555 requires all ducts to terminate at fire damper 
sleeves.

  •  Place the damper and attached retainer plate into the 

wall/floor opening.

  •  If a second retaining plate is being used, secure it on 

the opposite side of the wall/floor

 

Do Not PosItIoN RetaINeR Plate(s) IN 
FRaMe GRooVe

  •   Verify position, blade orientation, and actuator 

clearance then tighten the retainer plate clamping 
screws. The retainer plate(s) must overlap the wall/
floor opening a minimum of 1 inch (25mm). Secure 
the retainer plate(s) to the wall using appropriate 
fasteners (minimum #8 sheet metal screws) at the 
four corners of each retainer plate when two retainer 
plates are used and also within 3/4 in. (19mm) of the 
center of each plate when one retainer plate is used.

Summary of Contents for DFDR-XXX

Page 1: ...ntinuing research Greenheck reserves the right to change specifications without notice UL CLASSIFIED see complete marking on product UL CLASSIFIED to Canadian safety standards see complete marking on product UL Standard 555 Classification R13317 DFDR XXX SSDFDR XXX FDR XXX and SSFDR XXX Model Dampers are intended for installation in accordance with fire damper requirements established by National ...

Page 2: ...red to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper Excessive dirt or foreign material deposits on damper can cause torque requirements to exceed damper design 7 Caulking is not allowed between the damper sleeve and the wall or floor opening annular space However caulking may be applied to the retaining plates and a field applied sealant may b...

Page 3: ...BLY TO WALL AND FLOOR OPENINGS Damper assemblies must be installed in wall floor openings using a single retaining plate on either side of the wall floor or by using a retaining plate on both sides of the wall floor The use of a second retaining plate is allowed but is not necessary A single retaining plate is provided with the dampers A second retaining plate can be ordered as an option The retai...

Page 4: ...P D BYJNVN XPPE TUVET JO P D BYJNVN XPPE TUVET JO Fig 4 4 DFDR XXX Blade Orientation Normal 30 Off Horizontal Maximum 30 Off Horizontal Maximum Axle Axle Axle 30 30 Round duct connections shall be attached with 8 sheet metal screws as follows Ducts 22 in 559mm dia and smaller shall have three screws Ducts larger than 22 in 559mm dia and up to including 24 in dia shall have five screws NOTE All bre...

Reviews: