background image

3

Ceiling Exhaust and Inline Fans

Ceiling Radiation Damper (CRD)

If fan is to be used in a fire resistive membrane 
ceiling, a ceiling radiation damper must be used.

If the ceiling radiation damper is already mounted to  
the fan from the factory, proceed to Install the Fan.

Attachment Tabs

B-Models

To mount the ceiling radiation damper to fan, make sure 
grille attachment tabs are facing down. Then place the inlet 
part of the fan into the ceiling radiation damper collar, and 
use self-tapping sheet metal screws (by others) to screw 
through the damper collar and into the fan housing. If the 
fan/light combination is being used, make sure ceiling 

radiation damper has 
an electrical plug in it. 
The electrical plug must 
be inserted into the fan. 
Make sure the electrical 
wire will not interfere with 
damper operation as 
shown in figure below.

Discharge Installation SP-A 50-90 Models

A-50-510, 710, 780 Models

Wires from lighted grille

Wires to ceiling fan

Do not allow
interference 
in this area

A-700, 900-1550 Models

SP-A Box Slot

Plastic SP-A
Duct Adapter Tabs

Insert plastic duct tab into SP-A box slots.

 

Plastic SP-A  
Duct Adapter (PN 473322)

Sheet Metal Screw #10x3/8

 

Phillips Head (PN 415838)

SP-A Box

Sheet Metal Screw #10x3/8

Phillips Head (PN 415838)

SP-A Box

Plastic SP-A

 

Duct Adapter (PN 473322)

Screw Tabs

Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)

Screw holes

Rotate plastic SP-A duct adapter (PN 473322) 
until the screw tabs meets SP-A box.

1

2

Install screws provided to secure discharge.

3

®

Summary of Contents for CSP

Page 1: ...necting means to prevent power from being switched on accidentally When the service disconnecting means cannot be locked securely fasten a prominent warning device such as a tag to the service panel Installation work and electrical wiring must be done by qualified person s in accordance with all applicable codes and standards including fire rated construction Sufficient air is needed for proper co...

Page 2: ...A Models Only A 50 500 710 780 Models Remove the two screws holding the power assembly in and pull power assembly out Rotate power assembly 180 degrees and put back into fan Use the same screws to reattach power assembly to fan housing Flip fan over and remove the four screws holding the discharge duct and damper assembly Exchange the assembly with plate mounted on top of fan as shown in these ill...

Page 3: ...iation damper has an electrical plug in it The electrical plug must be inserted into the fan Make sure the electrical wire will not interfere with damper operation as shown in figure below Discharge Installation SP A 50 90 Models A 50 510 710 780 Models Wires from lighted grille Wires to ceiling fan Do not allow interference in this area A 700 900 1550 Models SP A Box Slot Plastic SP A Duct Adapter...

Page 4: ...two SP B mounting tabs fully engage into the two SP B box mounting slots 1 2 OPTIONAL Align the pins on the TR 6x4 adaptor to the duct pin hole on the SP B 6 inch duct Push until the adaptor snaps into place 3 SP B Box Scroll Slots SP B Box Mounting Tabs SP B Box Mounting Slots TR 6x4 Pin TR 6x4 PN 473324 SP B 6 inch Plastic Duct PN 474433 SP B Plastic Duct Pin Hole SP B Box Scroll Tabs ...

Page 5: ...height is determined shown in Fig 2 Cut hole to dimensions shown in table below 3 Installation of ductwork is critical to the performance of the fan shown in Fig 5 Straight ductwork 1 or ductwork that turns in the same direction as the wheel 2 is recommended Ductwork turning opposite the wheel direction 3 will cause turbulence and back pressure resulting in poor performance 4 Slide ductwork over t...

Page 6: ...wn are UL and cUL listed E 33599 Attach the Grille 1 If lighted grille is being used plug wire into fan socket If lighted grille and ceiling radiation damper are being used plug wire from lighted grille into ceiling radiation damper socket Do not plug wire directly into the fan socket Make sure the wire does not interfere with the ceiling radiation damper operation 2 Attach grille with two screws ...

Page 7: ... cleaned periodically to maintain performance Greenheck offers washable aluminum mesh filters specifically designed for these fans Please consult our SP CSP catalog for more information Flex Duct Connections Fiberglass Ductboard Remote Mounted Correct Low Sound Installation Incorrect SP and SP C Mounted Directly Overhead CSP and SP C Converted to Inline General Maintenance Suggestions Model SP CSP c...

Page 8: ...in the Library under Warranties Greenheck SP and CSP catalog provides additional information describing the equipment fan performance available accessories and specification data Phone 715 359 6171 Fax 715 355 2399 E mail gfcinfo greenheck com Website www greenheck com Our Commitment AMCA Publication 410 96 Safety Practices for Users and Installers of Industrial and Commercial Fans provides additio...

Reviews: