Damper Sleeve Dimensional Data

The drawings below and corresponding table show the position of the FSD-M211 damper when mounted in a factory sleeve. 

The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for installation 

of retaining angles and duct connections. 

 

127mm

Right hand drive is shown

Left hand drive available upon request

LH

RH

A

Sleeve Length

Varies

 

B*

S

T*

152mm

38mm max.

95mm

137mm

The "A" dimension is the location of the damper mounted 

in a factory sleeve. The table below shows the Standard, 

Minimum, and Maximum “A” dimensions.

Specifications

Combination  Fire  Smoke  Dampers  meeting  the  following  specifications  shall 

be  furnished  and  installed  where  shown  on  plans  and/or  as  described  in 

schedules. Dampers shall meet the requirements of the latest edition of NFPA 

80, 90A, 92A, 92B, 101, and 105.

Dampers  shall  be  tested ,  rated  and  labeled  in  accordance  with  the  latest 

edition of UL Standards 555 and 555S. Dampers shall have a UL 555 fire rating 

of  11⁄2  hours.  Each  damper  shall  be  equipped  with  a  heat  responsive  device 

which  has  been  tested  and  approved  for  use  with  the  damper  assembly  in 

accordance with UL 555. The heat responsive device shall have a temperature 

rating of (specifier select one of the following) 74°C, 100°C, or 177°C. Dampers 

shall  be  UL  labeled  for  use  in  dynamic  systems.  The  damper  shall  have  a 

dynamic  closure  airflow  rating  equal  to  or  greater  than  the  airflow  at  the 

damper’s installed location and a dynamic closure pressure rating of 1 kPa.

Dampers  shall  have  a  UL  555S  Leakage  rating  of  Class  I  and  a  Temperature 

rating of 177°C. Dampers shall have a UL 555S operational airflow rating equal 

to or greater than the airflow at its installed location and an operational pressure 

rating of 996 Pa. Damper actuators shall be factory mounted and qualified for 

use  with  the  damper  in  accordance  with  UL  555S.  Damper  actuators  shall 

be  (specifier  select  one  of  the  following)  electric  type  for  120  (24  or  230)  volt 

operation or pneumatic type for 25 psi minimum (30 psi maximum) operation.  

Manufacturers  submittal  data  shall  indicate  actuator  space  requirements 

around the damper.

All  UL  555  and  555S  Dynamic  Closure  Ratings,  Operational  Ratings  and 

Leakage  Ratings  shall  be  qualified  for  airflow  and  pressure  in  either  direction 

through the damper. UL ratings shall allow for mounting damper vertically (with 

blades running horizontal) or horizontally.

The  Damper  Manufacturers  submittal  data  shall  certify  all  air  performance 

pressure drop data is licensed in accordance with the AMCA Certified Ratings 

Program for Test Figures 5.2, 5.3 and 5.5.  Damper air performance data shall 

be developed in accordance with the latest edition of AMCA Standard 500-D. 

Dampers shall be labeled with the AMCA Air Performance Seal.

Damper blades shall be 1.5mm galvanized steel 3V type with three longitudinal 

grooves  for  reinforcement.  Blades  shall  be  completely  symmetrical  relative  to 

their axle pivot point, presenting identical resistance to airflow and operation in 

either direction through the damper (blades that are non-symmetrical relative to 

their axle pivot point or utilize blade stops larger than 13mm are unacceptable).

Damper  frames  shall  be  galvanized  steel  formed  into  a  structural  hat  channel 

shape  with  reinforced  corners.  Bearings  shall  be  sintered  bronze  sleeve  type 

rotating in extruded holes in the damper frame. Jamb seals shall be stainless 

steel compression type.

Basis of design is Greenheck Model FSD-M211.

Copyright © 2008 Greenheck Fan Corporation

FSD-M211 Rev. 6 January 2008

The following figures show maximum damper section size.

H

W

Single Section

A

127mm

.

305mm*

152mm

 

.

 

127mm

A

Sleeve Length

Varies

 

38mm max

95mm

137mm

Damper Sizing Information

*With the exception of dampers 10 in. high (254mm) or less. 

NOTE: Entire damper frame is not required to be installed within the 

wall. The damper blades, when closed should be contained within 

the wall.

in. (mm)

"A" Dimension

Standard

Maximum

All Dampers*

7 3/16 (183)

12 (305)

When H is 11 in. (279mm) or 

less with OCI, RRL, or TOR

12 (305)

12 (305)

Summary of Contents for Combination Fire Smoke Dampers FSD-M211

Page 1: ...truded silicone rubber blade seals Flexible stainless steel jamb seals Closure Device 74 C RRL Linkage Concealed in jamb Axles 13mm diameter plated steel Bearings Bronze sleeve type Size Limitations Minimum Size 101mm W x 101mm H Maximum Size Single Section 813mm W x 1270mm H or 914mm W x 914mm H Multiple Section 3251mm W x 2540mm H Vertical or 3658mm W x 2438mm H Horizontal Optional Features Stai...

Page 2: ...AMCA Test Figures Figure 5 3 Illustrates a fully ducted damper This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper Figure 5 2 Illustrates a ducted damper exhausting air into an open area This configuration has a lower pressure drop than Figure 5 5 because entrance...

Page 3: ... 1 10 7 6 22 10 2 42 12 7 65 15 3 95 17 7 127 20 3 167 305mm x 1219mm Velocity m s Pressure Drop Pa 2 5 3 5 1 15 7 6 32 10 3 57 12 9 90 15 3 125 18 174 20 5 227 1219mm x 305mm Velocity m s Pressure Drop Pa 2 5 8 5 1 27 7 7 57 10 3 105 12 9 164 15 6 242 17 9 316 20 7 424 R Greenheck Kunshan Co Ltd and Greenheck Fan Corporation certifies that the model FSD M211 shown herein is licensed to bear the A...

Page 4: ...Pressure Drop Pa 2 5 5 5 1 20 7 6 40 10 1 72 12 7 112 15 3 164 18 227 20 6 299 AMCA 5 3 Pressure Drop FSD M211 5D 6D 5D D 4 W H 3 14 Figure 5 3 Figure 5 2 Figure 5 5 NN Y NN NN Y NN NN Y NN NN Y NN NN Y NN 13 4463 301 1 4 4 7 0 5 5 34 4 0 7 0 5 74 13 4463 301 Y Y Y Y Y R Greenheck Kunshan Co Ltd and Greenheck Fan Corporation certifies that the model FSD M211 shown herein is licensed to bear the AM...

Page 5: ... 264 15 3 381 17 9 521 20 8 707 AMCA 5 5 Pressure Drop FSD M211 D 4 W H 3 14 2 5 10 30 10 100 1000 305mm x 305mm 610mm x 610mm 914mm x 914mm 305mm x 1219mm 1219mm x 305mm PRESSURE DROP PASCALS FACE VELOCITY METERS SECOND AMCA 5 5 VELOCITY VS PRESSURE DROP 3 0 5 x 3 0 5 1 2 1 9 x 3 0 5 6 1 0 x 6 1 0 3 0 5 x 1 2 1 9 9 1 4 x 9 1 4 R Greenheck Kunshan Co Ltd and Greenheck Fan Corporation certifies tha...

Page 6: ... qualified for use with the damper in accordance with UL 555S Damper actuators shall be specifier select one of the following electric type for 120 24 or 230 volt operation or pneumatic type for 25 psi minimum 30 psi maximum operation Manufacturers submittal data shall indicate actuator space requirements around the damper All UL 555 and 555S Dynamic Closure Ratings Operational Ratings and Leakage...