background image

Pre-Installation Guidelines

The basic intent of a proper installation is to secure 
the AMS & AMD series damper into the opening in 
such a manner as to prevent distortion and disruption 
of damper operation. The following items will aid in 
completing the damper installation in a timely and 
effective manner.

1)  Check the schedules for proper damper locations 

within the building. Visually inspect the damper for 
damage.

2)  Lift or handle damper using sleeve or frame. Do 

not lift damper using blades, linkage, actuators, 
pick-ups, or jackshafting. When handling multiple 
sections 
assemblies, use 
sufficient support 
to evenly lift at 
each section 
mullion (see 
drawing). Do not 
drag, step on, 
apply excessive 
bending, twisting, 
or racking.

3)  Do not install 

screws in damper frame that will interfere with 
unexposed blade linkage and prevent damper 
blades from opening and/or closing.

4)  Damper must be installed into duct or opening 

square and free of twist or other misalignment. 
Damper must not be squeezed or stretched into 
duct or opening. Out of square, racked, twisted or 
misaligned installations can cause excessive leakage 
and/or torque requirements to exceed damper/
actuator design.

5)  Damper and actuator must be kept clean, dry and 

protected from dirt, dust and other foreign materials 
prior to and after installation. Examples of such 
foreign materials include but are not limited to:

 

a) Mortar dust

 

b) Drywall dust

 

c) Firesafing materials

 

d) Wall texture

 

e) Paint overspray

6)  Damper should be sufficiently covered as to prevent 

overspray if wall texturing or spray painting will 
be performed within 5 feet (1.5m) of the damper. 
Excessive dirt or foreign material deposits on 
damper can cause excessive leakage and/or torque 
requirements and inaccurate airflow measurement to 
exceed damper/actuator design.

7)  ACCESS: Suitable access (actuators maintenance, 

etc.) must be provided for damper inspection 
and servicing. Where it is not possible to achieve 
sufficient size access, it will be necessary to install a 
removable section of duct. 

Spreader Bar

Attachments

Multi section dampers

Electrical Guidelines

All wiring shall be done in accordance with the 
National Electrical Code ANSI/NFPA-70 latest edition, 
any local codes that may apply, and wiring diagrams 
developed in compliance with the job or project 
design and specifications. 

Important!

Electrical input may be needed for this equipment. 
This work should be performed by a qualified 
electrician. Verify power before wiring actuator. 
Greenheck is not responsible for any damage to, or 
failure of the unit caused by incorrect field wiring. To 
avoid causing death or serious bodily harm to building 
occupants, follow all instructions carefully. Dampers 
must close completely to preserve the integrity of the 
fire smoke separation.

Electrical Guidelines

AMD & AMS Series

2

®

Summary of Contents for AMD-42

Page 1: ...velocity of 300 fpm 1 5 m s is required Table of Contents Pre Installation Guidelines 2 Electrical Guidelines 2 Installation 2 10 Setup and Operation for AMS and AMD Series Without Factory Supplied Controller 3 Clearances Required Between Damper Sleeves and Wall Floor Openings 4 Installing Multiple Damper Section Assemblies 4 5 Multiple Section Damper Wiring 5 Maximum Assembly Tables 5 Inserting D...

Page 2: ...nstallation Examples of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 6 Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet 1 5m of the damper Excessive dirt or foreign material deposits on damper can cause excessive leakage and or...

Page 3: ...staller Design calculations for these retaining and supporting members should be determined by field engineers for that particular installation 4 Individual damper sections as well as entire multiple section assemblies must be completely square and free from racking twisting or bending Measure diagonally from upper corners to opposite lower corners of each section 5 Damper blades axles and linkage ...

Page 4: ...MS see example label below Using the high pressure limit of the transducer and the voltage output of the transducer the real time pressure reading can be calculated using the formula Ptransducer Transducer Output Voltage High Pressure Limit of Transducer 10 Formula 1 The pressure reading of the transducer can then be used to calculate the volumetric flow rate going through the AMS or AMD using the ...

Page 5: ...4 2590 8 2743 2 40 40 0 79 0 81 0 82 0 84 0 85 0 87 0 88 0 90 0 92 0 93 0 95 0 97 0 99 1 01 1 02 1 04 1 06 1 08 1 10 20 29 0 83 0 85 0 86 0 88 0 89 0 91 0 93 0 94 0 96 0 98 1 1 01 1 03 1 05 1 07 1 09 1 11 1 14 1 16 0 18 0 87 0 88 0 9 0 92 0 93 0 95 0 97 0 99 1 1 02 1 04 1 06 1 08 1 10 1 12 1 14 1 16 1 19 1 21 20 7 0 91 0 92 0 94 0 96 0 97 0 99 1 01 1 03 1 05 1 07 1 09 1 11 1 13 1 15 1 17 1 19 1 22...

Page 6: ...1 Setting the Flow Setpoint The controller accepts an analog input configurable for either 0 10 or 2 10 VDC that is proportional to a target volumetric airflow rate cfm The voltage corresponding to the setpoint can be determined using the following formulas 0 10 VDC setpoint C Q Vmax A 10 2 10 VDC setpoint C Q Vmax A 8 2 Formula 3 Where C Flow Setpoint VDC Q Desired Airflow cfm V max Maximum Velocity...

Page 7: ...ing the Damper Actuator The actuator can be powered either by the same power supply as the controller as shown in Figure 2 or by running a separate power supply to terminals 4 and 5 of the factory supplied terminal block on the AMD AMS In addition the Control Out from the controller terminal 7 must be run to terminal 6 on AMD AMS terminal block Connecting the Flow or position Setpoint Signal Conne...

Page 8: ...one at factory when the actuator is externally mounted When the actuator is internally mounted the actuator must be wired to the terminal block in the field Vari Green Constant Volume Controller Wiring Diagram Figure 2 AMD AMS Series 8 ...

Page 9: ... Elbow Without Vanes D 2 2D Round Sweep Elbow D 2 2D Sweep Elbow 3D Centrifugal Fan Discharge 1 5D Centrifugal Fan Inlet 5D Vane Axial Fan Discharge 2D Vane Axial Fan Inlet Optimal Placement for AMS AMD Damper Series Fans AMD AMS Series 9 ...

Page 10: ...ransitions 1D Į Į Transition 1 D 2 Į Į Transition 2 1D Į Į Transition 3 D 2 Transition 4 Į Į 1D Į Transition 5 1D Į Transition 6 1D Į Transition 7 D 2 Transition 8 Į Dampers 1D D1 4D D2 AMD AMS Series 10 ...

Page 11: ... D Duct Diameter 4 x Width x Height H Rectangular Duct D Air Handling Units 1D Louver Air Handler with Louver Hood Return Air 1D Takeoffs 3D Branch Takeoff 1 3D Branch Takeoff B2B 2D Branch Takeoff 3 1D Branch Takeoff 4 Branch Takeoff B2A AMD AMS Series 11 ...

Page 12: ...l bearings without grease fittings do not require lubrication Ball bearings with grease fittings require only minimal grease Closure Remove foreign materials that may be interfering with blade closure or effective sealing of the blades with each other or with the frame Operation While operating the damper through its full cycle check to see that the blades open and close properly If there is a probl...

Reviews: