Setting the Actuator/Controller’s
BACnet Configuration
The actuator’s BACnet configuration including the
device instance, MAC address, and baud rate can be
accessed through its Ethernet port .
Connecting to the Actuator
1 . Using an Ethernet cable, connect the CAT 5 Ethernet
port on your computer to the CAT 5 port on your
actuator .
2 . Go into your computer’s Control Panel and access
the Local Area Connection
Windows 7 or 8
• Access the Network and Internet settings then
the Network Sharing Center
• Click on Change adapter settings then right
click on the Local Area Connection and select
Properties
Windows XP
• Open Network Connections
• Right click on the Local Area Connection and
select Properties
Access IP Address Settings
1 . Select Internet Protocol
Windows 7 or 8
Select Internet Protocol Version 4 (TCP/IPv4)
the click on Properties
Windows XP
Select Internet Protocol (TCP/IP) the select
Properties
2 . Change the IP Address to the value shown below .
Then hit the Tab key and the Subnet mask will
populate . Then click OK .
Access the Actuator
1 . Open Internet Explorer and enter the following
address:
http://192.168.0.10:8080/index.html
2 . Enter “amdsetup” as the User Name and “gfcamd” as
the password .
Entering the BACnet Settings
1 . Click on BACnet/MP settings .
2 . Select MS/TP as Protocol
3 . Configure the desired baud rate and MAC address
4 . Choose unique Instance ID
5 . Enter desired Device Name (optional)
6 . Click Submit button
6
Air Measuring Dampers: AMD-XX-TD Series