Greengate TSW-MV-W Installation Instructions Download Page 2

Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com

Printed in Malaysia

Settings  

•  The tamper resistant time-on interval can be preset. In addition, a manual scroll-up mode can override the 

setting temporarily – this feature can be disabled, thereby providing a fixed interval timer.

•  A flicker of the lights and/or a beep warning begins 2 minutes before time-out (either or both can be disabled).

The TSW-MV is factory preset to meet newer energy code override mandates. No adjustment is required. This 

setting will provide a two hour maximum operating time before shut-off. The scroll feature is active to allow the user 
to change the operating time with the maximum time setting at two hours.

Close the timer door and the unit is ready. One press of the bottom cover turns the load ON. The load will stay ON 

until a count-down to the preset OFF time. Pressing the bottom cover again will turn load OFF.

SET FOR:

1. 4HR: Set ON for preset 4 hour maximum 

countdown when 2HR is set to OFF. (Also 
used in custom time programming.)

2. 2HR: Set ON for preset 2 hour maximum 

countdown when 4HR is set to OFF. (Also 
used in custom time programming.)

3. LIMIT: Used with programming sequence. 

Switch from ON to OFF to limit scroll to 
match custom time.

4. SCROLL: Set ON allowing the timer to scroll 

to a shorter run time. Set OFF to disable. 
Switch from ON to OFF to set a custom time. (Also used in programming sequence.)  
The time scrolls in steps: 
 

•  5 minute steps from 5 minutes to 1 hour 

 

•  10 minute steps from 1 to 4 hours 

 

•  30 minute steps from 4 to 12 hours 

 

•  1 hour steps from 12 to 24 hours

5. BEEPER: Set ON activating the feature for a beep warning every 15 seconds starting 2 minutes before OFF.
6. BLINK: Set ON activating a feature for load flash 2 minutes before OFF.

1. To turn load ON, press the START/STOP button momentarily. 

 

•  The LCD will display the countdown time interval selected. The time interval will start counting down.

Operation  

1. To test the unit, set the DIP Switch to the minimal time-out interval (5 minutes).
2. If the unit does not function: 

a.  Check the ground wire. Make sure the box has good ground and is attached properly. 
b.  Check all other wiring to make sure connection is secure. 
c.  Check if power is turned back on at the main circuit breaker panel. 
d.  If the unit still does not function, consult the factory.

3. If the load will not turn OFF automatically: 

a.  Check if the load goes ON/OFF when pressing START/STOP button. If not, check the red wire for good    
  connection. If load does go ON/OFF, consult the factory.

Please refer to www.coopercontrol.com under the Legal section for our terms and conditions.

Troubleshooting  

Warranties and Limitation of Liability  