Installation Instructions

Model # ONW-P-1001-MV-W

Model # ONW-P-1001-MV-V

Model # ONW-P-1001-MV-LA

Model # ONW-P-1001-MV-G

Model # ONW-P-1001-MV-B

NeoSwitch Passive Infrared (PIR)  

Single Relay Occupancy Sensing Wall Switch

(Ground Required)

•  Read all instructions on both sides of this  

sheet first

•  Install in accordance with ALL local codes
•  For indoor use only

General Information  

Technology:

 Passive Infrared (PIR)

Electrical Ratings   

120 VAC:

•  Incandescent/Tungsten – Max. load: 6.7 amps, 

800W, 50/60 Hz

•  Fluorescent/Ballast – Max. load: 10 amps, 1200W, 

50/60 Hz

Motor Load: ¼ HP @ 125 VAC
277 VAC:

•  Fluorescent/Ballast – Max. load: 9.8 amps, 

2700W, 50/60 Hz

Ballast Compatibility:

 Compatible with magnetic and 

electronic ballasts

No Minimum Load Requirement
Time Delays:

 Self-Adjusting, 15 seconds/test (10 min 

Auto), Selectable 5, 15, 30 minutes

Coverage:

 Major motion – 1000 sq. ft.

 

Minor motion –  300 sq. ft.

Light Level Sensing:

 0 to 200 foot-candles

Operating Environment:

•  Temperature: 32° F – 104° F (0° C – 40° C)
•  Relative Humidity: 20% to 90% Non-condensing

Housing:

 Durable, injection molded housing.  

Polycarbonate resin complies with UL94VO.

Size:

•  Mounting Plate/Strap Dimensions: 

4.195" H x 1.732" W (106.553 mm x 44 mm)

•  Product Housing Dimensions: 2.618" H x 1.752" 

W x 1.9" D (66.5 mm x 44.5 mm x 48.26 mm)

LED Indicators:

 Red LED indicates PIR detection;  Green 

LED acts as EcoMeter or night light locator.

Specifications  

Description  

Coverage  

The ONW-P-1001-MV Occupancy Sensing Wall Switch is a Passive Infrared (PIR) motion sensing lighting control 

and conventional Wall Switch all-in-one, used for energy savings and convenience.

PIR Technology

The sensor’s segmented lens divides the field of view into sensor zones, and detects the changes in temperature 

that are created when a person, or part of a person as small as a hand, passes into or out of a sensor zone.  

The ONW-P-1001-MV allows the control of one load with one occupancy sensor switch.  
The sensor can be configured to enhance energy savings by setting the unit for manual ON operation.
In Automatic ON Mode, the lights turn ON automatically when a person enters the room.   In Manual ON Mode, the 

lights are turned ON by pressing the universally recognized light icon Pushbutton.  In either mode, the lights stay ON 
as long as the sensor detects motion in the room.  When the room is vacated, the lights turn OFF automatically after 
a preset Time Delay interval.

The sensor includes self-adaptive technology that continually adjusts to conditions by adjusting sensitivity and 

Time Delay in Real-time.  By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the potential 
energy savings that are available in the particular application.

The EcoMeter provides a visual indicator of energy usage, increasing end user awareness and reminding 

individuals to take control of their lighting to maximize energy savings.

The Daylighting feature prevents lights from turning ON, when the room is adequately illuminated by natural light.  
Walk-Through feature maximizes energy savings by not leaving the lights ON after a momentary occupancy.  The 

sensor will switch the lights ON when it detects a person entering the area.  If the sensor does not continue to detect 
motion 20 seconds following the initial activation, it will automatically go to a shorter 2 minute Time Delay.

The ONW-P-1001-MV is designed for offices up to 300 square feet.

Location  

When installing the ONW-P-1001-MV in a new junction box, choose the switch location carefully to provide  

optimum coverage of the occupied area.  When replacing an existing Wall Switch, bear in mind that there must be a  
clear Line-of-sight between the sensor and the area to be covered.  Avoid pointing the ONW-P-1001-MV directly into the 
hallway where it may detect passers-by.

EcoMeter Operation

Load 1

EcoMeter LED

OFF

ON

ON

OFF

Action   

EcoMeter

Benefit

A person enters the space and 

the load is activated

OFF

The area is vacated and the 

lights turn OFF automatically

100%

Increased awareness of energy savings;  

Acts as a night light locator

A person turns the lights OFF 

manually upon exiting an area

100%

Increased awareness of energy savings and 

reminds individuals to take control of their 

lighting for additional savings;  Acts as a night 

light locator

The daylight feature prevents 

the lights from automatically  

turning ON when a person 

enters an area

100%

Increased awareness of energy savings and 

lets individual know that the daylighting 

feature is working

Wiring  

CAUTION:  Before installing or performing any service on a Greengate system, the power MUST be turned OFF 
at the branch circuit breaker.  According to NEC 240-83(d), if the branch circuit breaker is used as the main 
switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.”  All installations should be 
in compliance with the National Electric Code and all state and local codes.

NOTE REGARDING COMPACT FLUORESCENT LAMPS:  The life of some compact fluorescent lamps (CFLs) is 

shortened by frequent automatic or manual switching.  Check with CFL and ballast manufacturer to determine the 
effects of cycling.

1. Make sure power is turned OFF at the branch circuit breaker.
2. Wire units as shown in wiring diagrams per applicable voltage requirements. 
3. Mount unit to Wall Box.
4. Turn power back ON at the branch circuit breaker and wait 2 minutes for the unit to stabilize.
5. Make necessary adjustments.  (See Checkout and Adjustments section)
6. Install Wall Switch plate.

LOAD

120/277 VAC

BLACK

BLUE

NEUTRAL

GROUND

GREEN

Wiring Diagram 1:

 120/277 VAC single level single circuit wiring diagram

Installation  

The ONW-P-1001-MV can be installed in any standard single gang 

box.  It may be installed in the same manner as an ordinary Wall Switch.
 

•  Wire the ONW-P-1001-MV as described in the wiring section.  
•  Mount the ONW-P-1001-MV in the junction box.

,

36

20

,

Maximum coverage area may

vary somewhat according to room

shape and the presence of obstacles.

8

,

Minor Motion, IR

Major Motion, IR

P/N 9850-000344-01

Reviews: