background image

Limited Warranty

DIP Switch Settings

Troubleshooting

All products manufactured by Cooper Controls and identified with the Greengate brand are warranted to be free from defects in
material and workmanship and shall conform to and perform in accordance with Seller’s written specifications for a period of:  Five
(5) years from date of shipment for all occupancy sensors and Three (3) years from date of factory invoice for our hardware and
software on Lighting Control Panels.  We warranty all our standard relays for a period of 10 years from date of factory invoice.  We
guarantee  the  performance  of  our  system  to  specifications  or  your  money  back.    This  warranty  will  be  limited  to  the  repair  or
replacement, at Seller’s discretion, of any such goods found to be defective, upon their authorized return to Seller.  This limited
warranty does not apply if the goods have been damaged by accident, abuse, misuse, modification or misapplication, by damage
during  shipment  or  by  improper  service.    There  are  no  warranties,  which  extend  beyond  the  hereinabove-limited  warranty,
INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS.
No employee, agent, dealer, or other person is authorized to give any warranties on behalf of the Seller or to assume for the Seller
any other liability in connection with any of its goods except in writing and signed by the Seller.  The Seller makes no representa-
tion that the goods comply with any present or future federal, state or local regulation or ordinance.  Compliance is the Buyer’s
responsibility.  The use of the Seller’s goods should be in accordance with the provision of the National Electrical Code, UL and/or
other industry or military standards that are pertinent to the particular end use.  Installation or use not in accordance with these
codes and standards could be hazardous.

Cooper Controls
203 Cooper Circle, Peachtree City, GA 30269
800-553-3879
www.coopercontrol.com 

P/N 9850-000174-01

Checkout and Adjustment

Issue

Possible Causes

Suggestions

Lights 

Will Not

Turn ON 

automatically

Wall Switch OFF

Turn Wall Switch ON.

If low voltage switch option is used, lights may

have been turned-off manually.

Press low-voltage switch.

Daylight Feature Enabled

If all lights are required to turn ON adjust DIP Switch 10

and/or daylight potentiometer

Power interruption

Check incoming voltage and/or wiring

Lights 

Will Not 

Turn ON 

manually

Daylight Feature Enabled

If all lights are required adjust DIP switch 10 and/or daylight

potentiometer.

Power interruption

Check incoming voltage and/or wiring

If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879

Lights 

Will Not 

Turn OFF 

automatically

Override

Make sure sensor is not in Override Mode (DIP Switch 8 up).

Ultrasonic Sensitivity set High

Lower sensitivity by turning green potentiometer CCW in

small decrements.

Sensor installed close to an air vent 

Sensors should be installed minimum 4 - 6 feet away from

any air vent and out of path of heavy airflow.

Sensor installed close to indirect lighting.

Sensors should be mounted away from indirect lighting.

Self-adjust

It may be possible for the unit to have self-adjusted the time

delay to a 30 minute delay. If the lights do not turn OFF after

30 minutes follow next step.

30 Minute Delay

Maximum time delay is 30 Minutes. Check DIP Switches to

verify DIP Switch settings. If lights do not turn OFF at the set

time delay, check next step.

PIR activated by heat source other than occupant

Move DIP Switch 5 up.

Bypass

Check wiring to make sure sensor or switchpack are not

bypassed.

Lights Will Not 

Turn OFF 
manually

Override

Make sure sensor is not in Override Mode (DIP Switch 8 up).

If lights will still not turn OFF, call Technical Services at 1-800-553-3879

LED Indicators Functionality

Adjustments should be made with the HVAC system ON. Use only insulated tools to make adjustments.

Self-Adjust 

Sensor is shipped in the Self-Adjust Mode. This applies to Time Delay, US, and PIR sensitivity. In preparation for

the Installer Test, the time delay is set to 15 seconds, after the sensor is installed, powered-ON and has stabilized,
the  unit  will  Time-out  15  seconds  after  the  last  motion  detected.  Coverage  and  sensitivity  can  be  confirmed  by
watching the Green (US) and Red (PIR) indicator LEDs on the front of the sensor, while moving around the room.

1. Walk around the room and monitor LEDs. LEDs should only turn ON for ¼ second with each motion. (If LEDs 

do not turn ON, go to Installer Adjustments - Sensitivity Adjustments Section)

2. Stand still six to eight feet away from the sensor for five seconds. LEDs should not turn ON. (If any LED turns ON,

note LED and go to Installer Adjustments – Sensitivity Adjustment section)

3. Walk outside the room and wait 15 seconds for the lights to turn OFF. (If lights do not turn OFF go to Installer 

Adjustments Section)

4. Re-enter the room to activate sensor. (If lights do not turn ON go to Troubleshooting Section)
5. The unit will remain in Test Mode for 10 minutes then automatically exit Test Mode and go for 10 min. Time 

Delay User Mode setting.

Note:

To place into Test Mode, toggle DIP Switch 10 out of its current position, wait 3 seconds, and then back in to its original position. To force into 

10 min User Mode move Dip Switches 1 and 2 down. (If DIP Switches 1 and 2 are already down, toggle DIP Switch 1 out of its current position, wait 3 sec-
onds, and then back to its original position) While in Test Mode, the LEDs will flash once per 1/4 second.

Sensitivity Adjustments

Ultrasonic Sensitivity (Green LED) – Using a small flathead screw driver turn the green potentiometer so that the arrow
points up.

1. Stand in different areas of the room and wave your hands.
2. If the Green LED does not turn ON, increase the US sensitivity by turning the green potentiometer clockwise in 

small increments. Repeat Step 1.

3. Stand still six to eight feet away from sensor for five seconds. LED should not turn ON.
4. If Green LED turns ON without motion or is constantly ON decrease the US sensitivity by turning the green poten-

tiometer counter-clock-wise in small decrements. Repeat Step 3.

PIR

Sensitivity

1. Stand in different areas of the room and wave your hands.
2. If the Red LED does not turn ON, check for any obstructions.
3. Stand still six to eight feet away from sensor for five seconds. LED should not turn ON.
4. If Red LED turns ON without motion or is constantly ON adjust PIR sensitivity to 50% by moving DIP Switch 5 up.

Field-of-view outside the space

1. Adjust PIR sensitivity to 50% by moving DIP Switch 5 up.
2. Adjust Ultrasonic Sensitivity.

Daylight Adjustments (-R Model Only 0 to 300 foot-candles)

If this feature is not needed, leave the light level at maximum (fully clockwise).

The Daylighting feature prevents the lights from turning ON when the room is adequately illuminated by natural light. If
there is enough light in the room regardless of occupancy, the sensor will hold the lights OFF. If there is not enough light
in the room, the sensor will allow the lights to turn ON when occupied.

Full and Half Logic Modes (See DIP Switch legend):
In both Full and Half Logic modes, lights connected to the yellow control lead will not turn ON upon occupancy acti-
vation, should the ambient light level exceed the preset foot-candle level.

After activation:

Full Logic Mode - should the ambient light level exceed the preset foot-candle level, the lights connected to the yel-

low control lead will turn OFF. The lights will remain OFF, until the ambient light level falls below the set point.

Half Logic Mode – the output state of the yellow control lead will not change with ambient light changes, after occu-
pancy activation. If the amount of natural light available rises above the setpoint, the daylight sensor will not turn the 
lights OFF while occupancy is being detected.

Note: Set the light level when the ambient light is at the level where no artificial light is needed. In order for this fea-
ture to function, the yellow control lead must be wired.

1.  With the load ON, put the sensor into Test Mode. To place into Test Mode, toggle DIP Switch 10 out of its current

position, wait 3 seconds and then back in to its original position.

2.  Set DIP Switch 10 to Full or Half Logic Mode.
3.  Set the Light level to Minimum (fully CCW).
4.  Leave the room and let the sensor Time-out so lights are OFF. Enter the space and lights should remain OFF.
5.  Make sure not to block the sensor from the daylight source and adjust the light level potentiometer CW in small 

increments until the lights are ON. (Pause 5 seconds between each adjustment)

6.  Once the lights are ON, the load connected to the sensor will not turn ON if light levels are above the current 

illumination.

Time Delay Adjustments

People who remain very still for long periods of time may need a longer Time Delay than the default setting of 10 min-

utes. As long as Auto is enabled, the sensor will respond to each pair of False-offs with no normal OFF in between, by
alternately making slight adjustments to either Time Delay (by 2 minute increments) or sensitivity, so there should be no
need for manual adjustment.  If manual adjustment is desired, refer to Time Delay settings in DIP Switch legend.

Reset  sensor  Time  Delay  to  factory  settings  by  moving  DIP  Switches  1  and  2  down.  (If  DIP  Switches  1  and  2  are

already down, toggle DIP Switch 10 out of its current position, wait 3 seconds, and then back to its original position)

Automatic Mode

In Automatic-ON Mode, the lights turn ON when a person enters the room. If optional momentary low voltage switches

are used along with Automatic-ON Mode, activating the switch(es) while the load is ON turns the load OFF. When the
load is turned OFF manually, as long as the sensor continues to detect occupancy the loads stay OFF. After the Time
Delay  expires,  the  lights  stay  OFF  and  the  sensor  goes  back  to  Automatic-ON  Mode.  For  wiring  information  for  the
optional momentary low voltage switch(es), please see the wiring section of the installation instructions.

Manual Mode (-R Model Only)

In Manual-ON Mode, the optional momentary low voltage switch(es) is required to turn the load(s) ON. Once activated

the sensor will maintain the lights ON until motion ceases and the Time Delay expires. While the room is occupied the
BAS relay remains active. After the Time Delay expires, the load(s) will automatically be turned OFF and the switch(es)
must be used to turn the load(s) ON unless there is motion detected within the 10 second re-trigger period.

Lighting Sweep Option

If  selected,  this  DIP  Switch  option  forces  an  initial  60  second  delay  upon  “power  up”  to  prevent  false  activation  in

buildings with computer control systems.
1. Move DIP Switch 9 up. If not selected (Dip Switch 9 down), upon initial “power up” or restoration of power the sen-

sor will force the lights ON no matter the state of occupancy.

HVAC/Tracking Mode (-R model only)

If selected, Tracking Mode allows the load connection to the Form C relay to follow the state of the sensor’s blue lead.

HVAC  Mode  allows  the  load  connected  to  the  Form  C  relay  to  remain  ON  when  the  lights  are  turned  OFF  manually.
Applications may include keeping the room at a desired temperature while giving a presentation and the lights are OFF.

Zero Time Delay Mode

In Zero Time Delay Mode, the output is actuated for one second to signal another device that the space being moni-

tored is occupied. Applications may include the use of a lighting control system to manage the delay of the lighting deac-
tivation. Please see the wiring diagram section for wiring details.

When in Zero Time Delay Mode and Tracking Mode the load connected to the Form C relay shall follow the state of

the sensor’s blue lead (zero Time Delay for the form C relay).

When in Zero Time Delay Mode and HVAC Mode, the load connected to the Form C relay remains ON for the standard

Time Delay. 

Override

The Override setting allows the lights to remain ON in the unlikely event of sensor failure.

1. Move DIP Switch 8 up.

While in Override Mode, the optional low voltage momentary switch(es) will toggle the lighting load(s). 

Printed in Malaysia

Installer Adjustments

(-R model only)

Sweep

Override

LEDs

(-R model only)

(-R model only)

(-R model only)

Full/Half Logic HVAC/Tracking

Zero Time Delay

Pot 1 - Blue (0-300 FC)

Ultrasonic

(-R model only)

Pot 2 - Green

During Installer/Test Mode

LEDs will flash once per ¼ second

LEDs will flash once per second

While in User Mode

10 to 30 minutes

LED Flashing Speed

Duration

10 minutes

1 2 3 4 5 6 7 8 9 10 11 12

ON

Daylight Sensor Adjustment

Ultrasonic Sensitivity Adjustment

PIR Detector

Reviews: