Air-to-water Heat Pump Split Versati
10
SPLIT TYPE
3. Nomenclature
G
RS
-
C
Q
10
Pd
/
Nh
H
-
M
(O)
1
2
3
4
5
6
7
8
9
10
NO.
Description
Options
1
GREE
G-GREE
2
Air to water heat pump
RS
3
Heating Mode
S= Static; C=Circulating
4
Function
Q=Multi-function; Omit=Single-function
5
Nominal Heating Capacity
8.0=8.0kW;10=10kW;
6
Compressor Style
Pd=DC Inverter; Omit=On/Off
7
Refrigerant
Nh=R32
8
Design Serial Number
B,C,D,E......
9
Power Supply
M=400V 3N~,50Hz; E=230V,~,50Hz
10
Indoor and Outdoor Unit Code
I=Indoor unit; O=Outdoor unit
Model Line-Up
Model Name
Capacity
Power supply
Heating
1
,kW
Cooling
2
,kW
GRS-CQ8.0Pd/NhH-M
8
8.5
400V 3N~,50Hz
GRS-CQ10Pd/NhH-M
10
10
GRS-CQ12Pd/NhH-M
12
11
GRS-CQ14Pd/NhH-M
14
12.6
GRS-CQ16Pd/NhH-M
15.5
13
GRS-CQ12Pd/NhH-E
12
11
230V,~,50Hz
GRS-CQ14Pd/NhH-E
14
12.6
GRS-CQ16Pd/NhH-E
15.5
13
Notes
(a)
1
Capacities and power inputs are based on the following conditions:
Indoor Water Temperature 30°C/35°C, Outdoor Air Temperature 7°C DB/6°C WB;
(b)
2
Capacities and power inputs are based on the following conditions:
Indoor Water Temperature 23°C/18°C, Outdoor Air Temperature 35°C DB/24°C WB.
Operation Range
Mode
Heat Source Side Temperature (°C)
User Side Temperature (°C)
Heating
-25~35
20~60
Cooling
10~48
7~25
Water Heating
-25~45
40~80