Multi Variable Air Conditioners Ducted Type Indoor Unit
5
Material type
Total length of
communication
line between
indoor unit and
wired controller L
(m/ft.)
Wire size
(mm
2
/AWG
)
Material
Standard
Remarks
Light/Ordinary
polyvinyl chloride
sheathed cord.
(60227 IEC 52
/60227 IEC 53)
L≤250m
(L≤820-1/5ft.)
2×0.75~2×1.25
(2×AWG18~2×A
WG16)
IEC
60227-5
1. Total length of communication
line can't exceed 250m (820-
1/5ft.).
2. The cord shall be Circular
cord (the cores shall be
twisted together).
3. If unit is installed in places
with intense magnetic field or
strong interference, it is
necessary to use shielded
wire.
3.3.2 Select Communication Line for Indoor Unit and Outdoor Unit
Fig 3.3.2
Material Type
Total Length L
(m/ft.) of
Communication
Cable between
Indoor Unit and
Indoor (Outdoor)
Unit
Wire size
(mm
2
/AWG
)
Material
Standard
Remarks
Light/Ordinary
polyvinyl
chloride
sheathed cord.
(60227 IEC 52
/60227 IEC 53)
L≤1000m
(L≤3280-5/6ft.)
≥2×0.75
(≥2×AWG18)
IEC 60227-5
1. If the wire diameter is enlarged to
2×1 mm
2
(2×AWG16), the total
communication line length can reach
1500 m (4921-1/4ft.).
2. The cord shall be Circular cord (the
cores shall be twisted together).
3. If unit is installed in places with
intense magnetic field or strong
interference, it is necessary to use
shielded wire.
3.4 Electric Installation
Model
Power Supply
MCA(A)
MOP(A)
GMV-ND07PLS/A-T(U)
208/230V-1ph-60Hz
1
15
GMV-ND09PLS/A-T(U)
1
15
GMV-ND12PLS/A-T(U)
1
15
GMV-ND14PLS/A-T(U)
1
15
GMV-ND18PLS/A-T(U)
1
15
GMV-ND22PLS/A-T(U)
1
15