Indoor Drain Piping
The Crown indoor wall unit uses a gravity drain system. There is no internal condensate pump.
The drain hose must slope downward with no kinks, raises or fluctuations.
NOTE:
The drain tube cannot be field re-located from the Left to the Right side of the indoor unit.
PIPING INSTALLATION
1. Connect the field supplied drain hose to the
outlet pipe of indoor wall unit. A field supplied
transition or adapter may be required.
2. Apply pipe insulation to the entire drain line
and joints to prevent sweating.
3. The through-wall hole for the drain hose must be lower than the indoor wall unit drain
outlet for a functional gravity drain system.
4. Install field supplied drain hose with a downward slope from the Indoor wall unit drain
outlet to the drain hose outlet.
5. Route the condensate drain hose in the safety location to dispose of the condensate water.
The drain hose
cannot raise upward.
The drain hose
slopes downward.
The drain hose
cannot raise upward.
Correct Incorrect Incorrect
Drain hose
Drain hose
Insulate
drain hose
Outlet pipe