Super Free Match Series
26
Memory card error
Flash 16 times
EE
Compressor demagnetizing
protection
Flash 17 times
HE
HE
Compressor desynchronizing
Flash 18 times
H7
H7
Compressor phase lack
Flash 19 times
U2
U2
Compressor phase circuit detection
error
Flash 20 times
U1
U1
Compressor power protection
Flash 21 times
L9
L9
Compressor discharge temperature
protection
Flash 23 times
E4
E4
Lack of refrigerant or jam protection
Flash 31 times
F0
F0
Normal operation
Flash 1 time
Frequency limitation for AC current
Flash 2 times
F8
Oil returning
Flash 3 times
F7
Defrosting
Flash 4 times
H1
H1
Frequency limitation for IPM
temperature
Flash 5 times
EU
Frequency limitation for PFC
temperature
Flash 6 times
EU
Frequency limitation for compressor
overload
Flash 8 times
LU
Frequency limitation for compressor
discharge temperature
Flash 9 times
F9
Frequency limitation for low pressure
Flash 10 times
Pn
Frequency limitation for high
pressure
Flash 11 times
F6
Discharge temperature sensor error
Flash 12 times
F5
F5
Outdoor temperature sensor error
Flash 13 times
F3
F3
Suction temperature sensor error
Flash 15 times
dc
Condenser temperature sensor error
Flash 16 times
A7
A7
Low pressure sensor error
Flash 18 times
dL
High pressure sensor error
Flash 19 times
e1
Fan motor error for indoor unit
Flash 20 times
H6
H6
Driving board is connected
Flash 1 time
Testing board is connected
Flash 2 times
Computer is connected
Flash 4 times
Indoor unit 1 is connected
Flash 5 times
Indoor unit 2 is connected
Flash 6 times
Indoor unit 3 is connected
Flash 7 times
Indoor unit 4 is connected
Flash 8 times
Indoor unit 5 is connected
Flash 9 times
Middle pressure sensor error
FU
Intermediate vapor injection
temperature sensor error
Fb