Unitary Ducted Split AC
12
5.1.2 Indoor Unit
C
D
E
A
B
Fig. 21 Indoor Unit Diagram
Table 7-Dimension of Indoor Unit
Unit: Inch
Model
A
B
C
D
E
HNF18024-D
21"
21-5/16"
10-3/4"
11-5/16"
43-1/2"
HNF18036-D
21"
21-5/16"
12-1/4"
11-5/16"
48-3/16"
HNF18042-D
24-1/2"
21-5/16"
13-3/4"
11-1/2"
48-3/16"
HNF18048-D
24-1/2"
21-5/16"
13-3/4"
11-1/2"
48-3/16"
5.2 Installation Recommendations
NOTE:
In some cases noise in the living area has been traced to gas pulsations from improper
installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb
customer.
2. Ensure that vapor and liquid tube diameters are appropriate for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable
silicon--based caulk.(See Fig. 22.)
6. Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and
walls.
7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes
in direct contact with tubing. (See Fig. 22.)
8. Ensure that tubing insulation is pliable and completely surrounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing
insulation. (See Fig. 22.)
10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of
insulation.
When outdoor unit is connected to factory--approved indoor unit, outdoor unit contains system