6TQWDNGUJQQVKPI
Y
N
Y
N
N
Y
N
N
Y
N
Y
N
Y
Y
Start
Did the equipment operate
normally before the failure
occurs?
The AP1 voltage
detection circuit
is at fault
Check wiring inside of
the indoor and outdoor
units
Are wires broken?
Check the communication
circuit of the outdoor unit
If the fault is eliminated?
The communication
circuit is abnormal
Replace the main board of
the indoor unit
End
If the fault is eliminated?
Replace the main board
AP1
of the outdoor unit
If the fault is eliminated?
Is the connection right?
Check the wiring of the indoor and
outdoor units with reference to the
wiring diagram
Correctly connect the
corresponding wires for
the indoor and outdoor
units with reference to
the wiring diagram
(8) Communication malfunction: (following AP1 for outdoor unit control board)
Mainly detect:
Detect the indoor and outdoor units connection wire and indoor and outdoor units inside wiring is connect well or not.
if is there any damage?
Is there any damage for the indoor unit mainboard communication circuit? Is communication circuit damaged?
The flow chart for malfunction detect:
Summary of Contents for GWH18RC-K3DNA1A
Page 15: ... QPUVTWEVKQP 8KGYU RQVWUXFWLRQ 9LHZV QGRRU 8QLW ĭ ĭ 0RGHO 8QLW PP ĭ ĭ ...
Page 16: ... QPUVTWEVKQP 8KGYU 2XWGRRU 8QLW 8QLW PP ...
Page 40: ... ZRNQFGF 8KGYU CPF 2CTVU KUV SORGHG 9LHZV DQG 3DUWV LVW QGRRU 8QLW 0RGHOV 5 1 5 1 5 1 ...
Page 42: ... ZRNQFGF 8KGYU CPF 2CTVU KUV 0RGHO 5 1 ...
Page 50: ... ZRNQFGF 8KGYU CPF 2CTVU KUV 2XWGRRU 8QLW 0RGHO 5 1 2 ...
Page 52: ... ZRNQFGF 8KGYU CPF 2CTVU KUV 0RGHO 5 1 2 ...
Page 55: ...6TQWDNGUJQQVKPI 0RGHO 0RGHO ...