DC Inverter U-match Series Duct Type Unit
20
(3) Install the hanger to the unit. See the following figure.
(4) Pass the unit hangers over the bolts installed to the ceiling and install the
unit with the special nut. See the following figure.
3.2.1.2 Leveling
After installing the indoor unit, level detection of the unit shall be conducted.
Place the unit horizontally and leave the left and right side with a downward slope of
1/100~1/50 in drainage direction, as shown below.