Aptitude requirement for maintenance man(repairs should be done only
be specialists).

a. All the work men who are engaging in the refrigeration system should bear the

valid certification awarded by the authoritative organization and the qualification for 
dealing with the refrigeration system recognized by this industry.

b. It can only be repaired by the method suggested by the equipment’s manufacturer.

If it needs other technician to maintain and repair the appliance, they should be 
supervised by the person who bears the qualification for using the flammable refrigerant.

Safety preparation work before installation

     The safety must be inspected before maintaining the appliances with the flammable 
refrigerant for reducing the flammable hazard to the lowest.
     Work shall be undertaken under a controlled procedure so as to minimise the risk of a 
flammable gas or vapour being present while the work is being performed.

Environment checking

Detection of flammable refrigerants

      All maintenance staff and others working in the local area shall be instructed on the 
nature of work being carried out. Work in confined spaces shall be avoided. The area 
around the workspace shall be sectioned off. Ensure that the conditions within the area 
have been made safe by control of flammable material.
      The area shall be checked with an appropriate refrigerant detector prior to and during 
work, to ensure the technician is aware of potentially toxic or flammable atmospheres. 
Ensure that the leak detection equipment being used is suitable for use with all applicable 
refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
      No person carrying out work in relation to a refrigeration system which involves 
exposing any pipe work shall use any sources of ignition in such a manner that it may lead 
to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, 
should be kept sufficiently far away from the site of installation, repairing, removing and 
disposal, during which refrigerant can possibly be released to the surrounding space. 
Prior to work taking place, the area around the equipment is to be surveyed to make sure 
that there are no flammable hazards or ignition risks. “No Smoking” signs shall be displayed.
      If any hot work is to be conducted on the refrigeration equipment or any associated 
parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry 
powder or CO

2

 fire extinguisher adjacent to the charging area. 

      Ensure that the area is in the open or that it is adequately ventilated before breaking 
into the system or conducting any hot work. A degree of ventilation shall continue during 
the period that the work is carried out. The ventilation should safely disperse any released 
refrigerant and preferably expel it externally into the atmosphere. 

      Under no circumstances shall potential sources of ignition be used in the searching 
for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) 
shall not be used.

Specialist’s Manual

3

2

Summary of Contents for GPC07AM-K5NNA2B

Page 1: ...5NNA2C GPC09AM K5NNA2B Thank you for choosing our product Please read this Owner s Manual carefully before operation and retain it for future reference If you have lost the Owner s Manual please conta...

Page 2: ...Pipe 28 Attached Sheet Electric Schematic Diagram 31 This marking indicates that this product should not be disposed with other household wastes throughout the EU To prevent possible harm to the envi...

Page 3: ...components that produced by other manufacturers 6 After verification the problem or dispute is caused by the quality specification or majeure 7 The damage is caused by natural calamities bad using en...

Page 4: ...floor area m 4 WARNING Appliance filled with flammable gas R290 Appliance shall be installed operated and stored in a room with a floor area The appliance shall be stored in a room without continuous...

Page 5: ...le the air conditioner by yourself Do not put or hang dripping objects above the air conditioner Keep children from playing or climbing on the air conditioner Children and disabled people are not allo...

Page 6: ...r conditioner at humid environment During operation close doors and windows to improve cooling effect Please keep air inlet and air outlet clean no obstacles to avoid noise and vibration Please put th...

Page 7: ...controller NOTICE Heat discharge pipe and other installation accessories can t be discarded 4 1 Controller panel Guide louver 3 Swing louver 4 Castor 5 Filter Joint 7 Heat discharge pipe 8 Window adap...

Page 8: ...el won t display Under ON status dual 8 nixie tube on control panel will display set temperature under cooling mode while it won t display under other modes Pressing this button can turn on or turn of...

Page 9: ...eed high speed auto fan low speed Fan button 4 Operation Introduction for Control Panel 6 Sleep button Press sleep button to enter into sleep mode If the controller operates at cooling mode after slee...

Page 10: ...function Set temperature Operation mode Auto mode Cool mode Dry mode Fan mode Heat mode TIMER ON TIMER OFF 1 On Off button 2 Mode button button 4 Swing button 5 Fan button 6 Sleep button 7 Timer butto...

Page 11: ...at Under this mode air conditioner operates under heating mode Press Fan Speed button can adjust the fan speed Cooling only unit won t receive heating mode signal If setting heat mode with remote cont...

Page 12: ...press timer button timer setting status will be quit after 5s If timer is confirmer press this button again to cancel timer 8 Health button Press this button to achieve the on and off of health and sc...

Page 13: ...ns simultaneously to set the lamp on or off and send the code After being energized the lamp is defaulted on 1 Press the back side of remote controller marked the cover of battery box along the arrow...

Page 14: ...tioner Clean outer case If there s dust on the surface of outer case please use soft towel to wipe it If the outer case is very dirty such as grease please use neutral abluent to wipe it Clean outer c...

Page 15: ...1 Disconnect power supply 2 Clean filter and outer case 3 Remove dust and sundries on the air conditioner 4 Eliminate accumulated water in chassis refer to the section of Drainage way for details 5 Ch...

Page 16: ...ether the set temperature is proper Whether door and window are closed Is plug loose Whether the air switch is trip ped off or fuse is burnt Is there s malfunction for the circuit Whether the unit is...

Page 17: ...ure In order to prevent cold air air conditioner will delay for a while to be started up which is the normal phenomenon It s the normal phenomenon Air conditioner is defrosting will resume operation N...

Page 18: ...in the unit ERROR CODE and high humidity environment if ambient temperature is too high power off the unit and then energize it for operation after the ambient temperature drops to 35 below blocked by...

Page 19: ...the air 2 The place with high frequency devices such as welding machine medical equipment 3 The place near coast area 4 The place with oil or fumes in the air 5 The place with sulfureted gas 6 Other p...

Page 20: ...wire and grounding wire of power socket 5 Be sure to cut off the power supply before proceeding any work related to electricity and safety 6 Do not put through the power before finishing installation...

Page 21: ...sory list Tools needed for installation cross screwdriver gauge straight screwdriver scissors saw pencil heat discharge pipe Joint Window adapter top Window adapter bottom remote controller user s man...

Page 22: ...re Hook Assemble the wire hook at the back of the unit with screws the direction of wire Wind the power cord around the wire hook direction of wire hook is upward direction of wire hook is downward sc...

Page 23: ...When the chassis is full with water the buzzer will give out 8 sounds and H8 is displayed to remind user to discharge water the unit will turned off about 2min latter and all buttons are invalid Turn...

Page 24: ...n a level surface and make sure garden hose is clear of any obstructions and is directed downward Placing portable on an uneven surface or improper hose installation may result in water filling up the...

Page 25: ...ttom of sash Foam seal B adhesive type 1 Connect the rain guards to the insect guard net Insert all three projections on each rain guard into the holes in the insect guard net 2 Attach the guard combi...

Page 26: ...panel Exhaust cover 20 5 37 4 37 4 56 7 2 Secure the window panel to the window stool with screws 1 Open the window sash and place the window panel on the window sill 1 Open the window sash and place...

Page 27: ...nt air and insects from getting into the room 5 Close the window sash securely against the Window panel 7 Attach the bracket with a screw Recommended Please lay a tabular material underneath the windo...

Page 28: ...seal B adhesive type 1 Connect the rain guards to the insect guard net Insert all three projections on each rain guard into the holes in the insect guard net 2 Attach the guard combined above to the w...

Page 29: ...anel Inner height of the window 37 4 950mm 56 7 1440mm Use the window panel the adjustment panel and the extension panel Window panel Exhaust cover 20 5 37 4 20 5 37 4 56 7 2 Secure the window panel t...

Page 30: ...the bracket with a screw Recommended Please lay a tabular material underneath the window panel in case you could not attach the rain guard or the window adapter properly due to the deep window sill Br...

Page 31: ...om fix them together press the clasp forcibly in to the groove clockwise clockwise joint window adapter heat discharge pipe 3 Insert joint of heat 4 Lead the exhaust hose outdoors discharge pipe the s...

Page 32: ...t it with other When installing heat discharge pipe should be as flat as possible Don t prolong heat discharge pipe 29 The discharge pipe is suggested to be installed according to below figure by the...

Page 33: ...from outdoors 3 Remove the window adapter Pull out and remove the window adapter by pushing down two PUSH markings and slide and close the exhaust cover in the window panel Optional 1 Remove joint Pre...

Page 34: ...te in cooling mode The Electric schematic diagram are subject to change without notice Please refer to which one on the unit R M OUTTUBE OUTTUBE TEMP RT3 TUBE TEMP TUBE REC RT2 RT1 DISPLAY BOARD SENSO...

Page 35: ...potentially toxic or flammable atmospheres Ensure that the leak detection equipment being used is suitable for use with all applicable refrigerants i e non sparking adequately sealed or intrinsically...

Page 36: ...all include initial safety checks and component inspection procedures If a fault exists that could compromise safety then no electrical supply shall be connected to the circuit until it is satisfactor...

Page 37: ...inguished remove refrigerant purge the circuit with inert gas evacuate purge again with inert gas open the circuit by cutting or brazing If a leakage of refrigerant is found which requires brazing all...

Page 38: ...mpletion of charging but prior to commissioning A follow up leak test shall be carried out prior to leaving the site Ensure that contamination of different refrigerants does not occur when using charg...

Page 39: ...order Empty recovery cylinders are evacuated and if possible cooled before recovery occurs The recovery equipment shall be in good working order with a set of instructions concerning the equipment tha...

Page 40: ...600005061860 GREE ELECTRIC APPLIANCES INC OF ZHUHAI Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 E mail gree gree com cn Web www gree com...

Reviews: