background image

Multi Variable Air Conditioners Duct Type Indoor Unit

 

 

Do not insert fingers or 
objects into air outlet or air 
return grille. 

 

Open the door and window 
frequently to keep good 
ventilation for avoiding 
oxygen deficit when gas 
heater or oil heater is used 
in the room. 

 

Never plug in or unplug the 
power plug directly to turn 
on or turn off the air 
conditioner. 

 

Once the air conditioner is 
turned on, it can be turned 
off only after it has 
operated for 5min at least; 
otherwise, it will affect the 
oil return of compressor. 

 

Do not allow children to 
operate this air conditioner. 

 

Do not operate this air 
conditioner with wet hands. 

 

The air conditioner can be 
cleaned only when it has 
been turned off and the 
power has been cut off; 
otherwise, it may cause 
electric shock or injury. 

 

Never spray or flush water 
towards the air conditioner; 
otherwise, malfunction or 
electric shock may happen. 

 

Do not expose the air 
conditioner to the moist or 
corrosive environment. 

 

Put through the power 8 
hours in advance before 
operation. Do not cut off the 
power when the air 
conditioner stops operation 
for only about one night 
(protect the compressor). 

 

Volatile liquid, such as 
diluent or gasoline, will 
damage the appearance of 
air conditioner. Only soft dry 
cloth and wet cloth dipped 
with neutral detergent can 
be used to clean the outer 
case of air conditioner. 

 

Under cooling mode, 
please don't set the room 
temperature too low; keep 
the temperature difference 
between indoor and 
outdoor within 5°C (41°F). 

 

If there are any abnormal 
circumstances (such as 
burning smell, etc.), please 
turn off the unit and cut off 
the main power supply 
immediately, and then 
contact Gree appointed 
service center. If those 
abnormal circumstances still 
exit, the unit may be 
damaged and it may lead to 
electric shock or fire hazard. 

 

Do not repair the unit by 
yourself. Wrong 
maintenance may cause 
electric shock or fire 
hazard. Please contact 
Gree appointed service 
center for help. 

Summary of Contents for GMV series

Page 1: ...EN ORIGINAL INSTRUCTIONS VER 01 2020 12 04 USER MANUAL GMV DUCT UNITS WITH FILTER PUMP GMV ND22 72PL B T GMV ND22 71PLS B1 T GMV ND18 71PLS C T...

Page 2: ...IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference...

Page 3: ...model according to actual using environment otherwise it may impact the using convenience 4 This product has gone through strict inspection and operational test before leaving the factory In order to...

Page 4: ...turer 3 After verification the defect of product is directly caused by corrosive gas 4 After verification defects are due to improper operation during transportation of product 5 Operate repair mainta...

Page 5: ...n 10 4 3 Installation and Test of Drain Pipe 11 4 4 Installation of Air Duct 15 4 5 Installation of Wired Controller 17 5 Wire Connection 17 5 1 Connection of Wire and Wiring Board Terminal 18 5 2 Pow...

Page 6: ...the safety of the power supply The air conditioner must be grounded reliably for avoiding electric shock Please do not connect the earthing wire to gas pipe water pipe lightning rod or telephone line...

Page 7: ...hock may happen Do not expose the air conditioner to the moist or corrosive environment Put through the power 8 hours in advance before operation Do not cut off the power when the air conditioner stop...

Page 8: ...ard An all pole disconnection device which has at least 3mm clearances in all poles and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules Gree Electric Applian...

Page 9: ...it 8 Tieline 6 Wrap the sponge at the connection position 9 Others User Manual 1 copy Loosen leaf of Instruction Manual 1 copy harmful substance content table Qualified Certificate 1 copy Bar Code 1 c...

Page 10: ...ians for the installation Do not connect power until all installation work is finished 3 3 Requirements for Communication Line NOTICE If the unit is installed in the place with strong electromagnetic...

Page 11: ...tic field or strong interference it is necessary to use shielded wire 3 3 2 Select Communication Line for Indoor Unit and Outdoor Unit Fig 3 3 Material Type Total Length L m feet of Communication Cabl...

Page 12: ...GMV ND72PL B T 6 1 0 1 0 GMV ND22PLS B1 T 6 1 0 1 0 GMV ND25PLS B1 T 6 1 0 1 0 GMV ND28PLS B1 T 6 1 0 1 0 GMV ND32PLS B1 T 6 1 0 1 0 GMV ND36PLS B1 T 6 1 0 1 0 GMV ND40PLS B1 T 6 1 0 1 0 GMV ND45PLS B...

Page 13: ...e same for both indoor unit and outdoor unit 3 If the supply cord is damaged it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard 4 I...

Page 14: ...2 486 GMV ND40 63PLS C T 1060 415 1010 200 462 486 GMV ND71PLS C T 1360 415 1310 200 462 486 4 1 2 Punching of Bolt Spots and Bolt Installation Punch holes on the installation area according to the 4...

Page 15: ...nlet Ceiling may have to be strengthened to make it level and to prevent it from vibration You may consult user or constructor for details If the ceiling is not strong enough you can install a beam br...

Page 16: ...er installation will lead to water leakage and furniture and other objects may get wet 4 You can buy local hard PVC pipe as drain pipe When connecting the pipe insert the end of PVC pipe into the drai...

Page 17: ...plate to make the pipe clamp and hose insulated as shown in Fig 4 10 metal clamp accessory thermal sponge accessory Fig 4 9 Unit mm Fig 4 10 4 When connecting several drain pipes follow the instructi...

Page 18: ...pipe joints Fig 4 13 Connection of downspout elbow Fig 4 14 Inserting pipe connection Fig 4 15 10 The installation height of raising pipe for drainage should be lower than 850mm The gradient from rai...

Page 19: ...shown in Fig 4 18 Remove the drain hose after finishing testing and then put on the plug of water tray 2 Spray 1L water on evaporator with sprayer as shown in Fig 4 19 2 Start the water to check if w...

Page 20: ...n order to prevent air leakage The design and construction of air duct should comply with national requirements The edge of air return duct is suggested to be more than 150mm away from the wall Add a...

Page 21: ...tallation of Air return Duct 1 Square flange is defaulted to be fitted on the back before ex factory Air return cover is on the bottom as shown in Fig 4 23 Fig 4 23 2 If air return from the bottom is...

Page 22: ...en filtered Fig 4 25 Fig 4 26 4 5 Installation of Wired Controller Please refer to User Manual of Wired Controller for the installation details NOTICE When installation is finished the unit must be te...

Page 23: ...munication line should be separated from the power cord and the connecting wire of IDU and ODU 12 If the project needs higher static pressure you can set it through the wired controller 5 1 Connection...

Page 24: ...ad the power cord across the rubber ring 3 Connect the power cord to the L N terminals and the grounding screw 4 Fasten the power cord with a wire clamp 2 For air conditioner that uses 3 phase power 1...

Page 25: ...n The matched resistance should be connected in parallel between terminal screw D1 and D2 as shown in Fig 5 5 5 4 Connection of Communication Line of Wired Controller 1 Open the cover of electric box...

Page 26: ...ler 4 One wired controller is able to control 16 indoor units at the same time shown in Fig 5 7 NOTICE When the wired controller is controlling multiple indoor units at the same time the indoor units...

Page 27: ...Multi Variable Air Conditioners Duct Type Indoor Unit 22 Fig 5 7...

Page 28: ...e air filter on the air inlet for cleaning Use a dust catcher or water to clean it If the filter is very dirty e g greasy you can clean it using warm water below 45 C that is mixed with mild detergent...

Page 29: ...Over high temperature of IDU module ob Temperature sensor error of IDU module oC IDU charging circuit error o0 Other drive error db Special Code Field Debugging Code 8 Troubleshooting If your air con...

Page 30: ...tion is located PRODUCER GREE ELECTRIC APPLIANCES INC OF ZHUHAI West Jinji Rd Qianshan 519070 Zhuhai China REPRESENTATIVE GREE Czech Slovak s r o Ko uli ova 778 39 619 00 Brno Czech Republic www greec...

Page 31: ...NOTES...

Page 32: ......

Reviews: