Multi Variable Air Conditioners Console Type Indoor Unit
8
5) Return by following the steps in reverse order (3>2>1).
2.4.2 Installation
Secure using 6 screws for floor installations (Do not forget to secure to the rear wall).
For wall installations, secure the mounting plate using 5 screws and the indoor unit using 4
screws.
The mounting plate should be installed on a wall which can support the weight of the indoor unit.
(1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely
level, and mark the boring points on the wall.
(2) Secure the mounting plate to the wall with screws.
Floor Installation
Casing
Wall Installation
195mm
Molding
6screws
6screws
(3) Once refrigerant piping and drain piping connections are complete, fill in the gap of the
through hole with putty. A gap can lead to condensation on the refrigerant pipe, and drain
pipe, and the entry of insects into the pipes.
(4) Attach the front panel and front grille in their original positions once all connections are
complete.
Flaring the pipe end:
(1) Cut the pipe end with a pipe cutter.
(2) Remove burrs with the cut surface facing downward so that the chips do not enter the pipe.
(3) Fit the flare nut on the pipe.
(4) Flare the pipe.
(5) Check that the flaring is properly made.