GMV DC Air Handler
6
Material Type
Total Length L of
Communication Cable
between Indoor Unit and
Indoor (Outdoor) Unit
Numbers ×
size
Remarks
Light/Ordinary
polyvinyl chloride
sheathed cord.
L≤1000m
(L≤3280
-7/8ft.)
≥2×AWG18
1. If the wire diameter is enlarged to 2×AWG16,
the total communication line length can
reach 1500 m (4921-1/4ft.).
2. The cord shall be Circular cord (the cores
shall be twisted together).
3. If unit is installed in places with intense
magnetic field or strong interference, it is
necessary to use shielded wire.
3.4 Wiring Requirements
Power Cord Size and Air Switch Capacity
Model
Power Cord Size
Minimum Circuit Ampacity
(A)
Maximum Overcurrent
Protection (A)
GMV-ND09A/B-T(U)
208/230V-1Ph-60Hz
3.0
15
GMV-ND12A/B-T(U)
3.0
15
GMV-ND18A/B-T(U)
3.0
15
GMV-ND24A/B-T(U)
4.0
15
GMV-ND30A/B-T(U)
4.0
15
GMV-ND36A/B-T(U)
5.0
15
GMV-ND42A/B-T(U)
5.0
15
GMV-ND48A/B-T(U)
8.7
15
GMV-ND54A/B-T(U)
8.7
15
GMV-ND60A/B-T(U)
8.7
15
(1) Use copper wire only as unit’s power cord. Operating temperature should be within its rated value.
(2) If the power cord is more than 15 m (49-1/4 ft.) long, please increase properly the sectional area of power cord
to avoid overload, which may cause accident.
(3) Above selection requirements: Power cord size is based on BV single-core wire (2~4pc) at 40° (104°F) ambient
temperature when laying across plastic pipe. Air switch is D type and used at 40°C (104°F). If actual installation
condition varies, please lower the capacity appropriately according to the specifications of power cord and air
switch provided by manufacturer.
(4) Install cut-off device near the unit. The minimum distance between each stage of cut-off device should be 3 mm
(1/8 inch) (The same for both indoor unit and outdoor unit).