Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

4.3 Drainage Pipe Installation and Drainage System Testing 

4.3.1 Notice for Installation of Drain Pipe 

(1)  It is not allowed to connect the condensate drain pipe into waste pipe or other pipelines 

which are likely to produce corrosive or peculiar smell to prevent the smell from entering 

indoors or corrupt the unit. 

(2)  It is not allowed to connect the condensate drain pipe into rain pipe to prevent rain water 

from pouring in and cause property loss or personal injury. 

(3)  Condensate drain pipe should be connected into special drain system for air conditioner. 

(4)  The drainage pipe should be short and the gradient downwards should be at least 

1%~2% in order to drain condensation water smoothly. 

(5)  The diameter of drainage hose should be bigger or equal to the diameter of drainage pipe 

joint. 

(6)  Install drainage pipe according to the following Fig.4.3.1.  and arrange insulation to the 

drainage pipe. Improper installation may lead to water leakage and damp the furniture 

and other things in the room. 

(7)  You can buy normal hard PVC pipe used as the drainage pipe. During connection, insert 

the end of PVC pipe into the drainage hole and then tighten it with drainage hole and wire 

binder. Can’t connect the drainage hole and drainage hole with glue. 

(8)  When the drainage pipelines are used for several units, the position of pipeline should be 

about 100mm  (4  inch)  lower than the drainage port of each unit. In this case, thicker 

pipes should be applied. 

 

Fig.4.3.1 

4.3.2 Drainage Pipe Installation 

(1)  Drainage pipe should have the same diameter or larger diameter than the  connecting 

pipes (PVC pipe, outside diameter 25mm (1 inch

), thickness≥1.5mm (1/16 inch)). 

(2)  Keep drainage pipe short and sloping downwards at a gradient of at least 1% for 

preventing forming air bubbles. 

(3)  If the gradient of drainage pipe could not meet the installation requirements, raising pipe 

should be applied. 

(4)  Insert the drainage hose into drain socket, tighten the metal clamp securely. 

(5)  Warp the sealing pad over drain hose and metal clamp for heat insulation. 

Summary of Contents for GMV-ND07TD/A-T

Page 1: ...Owner s Manual Original Instructions Commercial Air Conditioners Multi Variable Air Conditioners One way Cassette Type Indoor Unit Models GMV ND07TD A T U GMV ND09TD A T U GMV ND12TD A T U...

Page 2: ...ld well keep this manual 6 If this unit fails to operate normally please contact our service center as soon as possible and provide the following information 1 Content on the nameplate model number co...

Page 3: ...turer 3 After verification the defect of product is directly caused by corrosive gas 4 After verification defects are due to improper operation during transportation of product 5 Operate repair mainta...

Page 4: ...Drainage System Testing 9 4 4 Panel Installation 12 4 5 Installation of Wired Controller 13 5 Wiring Work 14 5 1 Connection of Wire and Patch Board Terminal 14 5 2 Power Cord Connection 15 5 3 Connec...

Page 5: ...en charging welding process Do charge nitrogen when welding the pipes 11 Never short circuit or cancel the pressure switch to prevent unit damage 12 As for the unit controlled by the wired controller...

Page 6: ...er for help Any personal injury or property loss caused by improper installation improper debug unnecessary repair or not following the instructions of this manual should not be the responsibility of...

Page 7: ...e remote controller 14 Tapping screw 2 Used for fixing the remote controller holder 3 2 Installation Position Selection 1 The appliance shall not be installed in the laundry 2 The location should be a...

Page 8: ...gulations 2 Only qualified personnel can carry out installation work please contact with local dealer before installation 3 Make sure all the installation work completed before energizing 3 3 Requirem...

Page 9: ...eld or strong interference it is necessary to use shielded wire 3 3 2 Selection of Communication Wire between Indoor Unit and Indoor Unit or Outdoor Unit Fig 3 3 2 Material Type Total Length L m ft of...

Page 10: ...ove sheet is based on ambient temperature of 40 104 4 The circuit breaker specification in above sheet is based on ambient temperature of 40 104 If the working condition is different please adjust it...

Page 11: ...er and lower sides of the hanger bracket The washer fixing plate will prevent the washer from falling 3 The usage of paper pattern Refer to paper pattern of installation for ceiling opening dimension...

Page 12: ...nd then tighten the flaring nut with hand as shown in Fig 4 2 1 2 Tighten the flaring nut with torque wrench Fig 4 2 1 Pipe diameter mm inch Torque N m 6 35 1 4 15 30 9 52 3 8 35 40 12 7 1 2 45 50 15...

Page 13: ...to the drainage pipe Improper installation may lead to water leakage and damp the furniture and other things in the room 7 You can buy normal hard PVC pipe used as the drainage pipe During connection...

Page 14: ...ation height of raising pipe for drainage should be lower than B The gradient from raising pipe towards drainage direction should be at least 1 2 If the raising pipe is vetical with the unit the raisi...

Page 15: ...e g water pump etc 2 In case of commissioning finished please energize the IDUs and switch to cooling or dry mode meanwhile the water pump operates you can check the draining through the drain socket...

Page 16: ...roper decorative panel installation could cause the following problems Fig 4 4 1 2 Ensure that its clearance free between decoration panel and ceiling board after installation if not please adjust the...

Page 17: ...les and then install the corresponding screw cover 4 Close the horizon lover connect the butt terminal and arrange the wires 5 After tightening screws reinstall the air inlet grille Fig 4 4 4 4 5 Inst...

Page 18: ...e communication wires should be separated from power cord and connection wire between indoor unit 8 Adjust the static pressure via wired controller according to site circumstance 5 1 Connection of Wir...

Page 19: ...it can t operate normally Fig 5 2 1 1 Detach the electric box lid 2 Let the power cord pass through the wiring through holes 3 Connect wires according to Fig 5 2 1 4 Fix the power cord with wiring cla...

Page 20: ...1 Open electric box cover of indoor unit 2 Let the communication wire go through the rubber ring 3 Connect the communication wire to terminal H1 and H2 of indoor 4 bit wiring board 4 Fix the communica...

Page 21: ...s that must be set as master one and slave one 4 One wired controller can control 16 indoor unitS in maximum at the same time as shown in Fig 5 5 1 1 The type of indoor units must be the same if they...

Page 22: ...Multi Variable Air Conditioners One way Cassette Type Indoor Unit 18 Fig 5 5 1...

Page 23: ...outlet of indoor and outdoor unit are blocked 2 Check if securely grounded 3 Check if all the power cord and communication cable are securely connected 4 Check if any error code displayed after energ...

Page 24: ...y leakage of electricity Input voltage is too low Defect of main PC board The unit stops after running for a while The inlet or outlet of ODU or IDU are blocked by obstacle Poor cooling effect The fil...

Page 25: ......

Reviews: