Multi Variable Air Conditioners Cassette Type Indoor Unit
6
3.4 Wiring Requirements
Power Cord Size and Air Switch Capacity
Model
Power Supply
MCA(A)
MOP(A)
GMV-ND07T/C-T(U)
208/230V-1ph-60Hz
0.8
15
GMV-ND09T/C-T(U)
0.8
15
GMV-ND12T/C-T(U)
0.8
15
GMV-ND15T/C-T(U)
0.8
15
GMV-ND18T/C-T(U)
1.0
15
GMV-ND22T/C-T(U)
1.0
15
GMV-ND24T/C-T(U)
1.0
15
GMV-ND30T/C-T(U)
2.0
15
GMV-ND36T/C-T(U)
2.0
15
GMV-ND42T/C-T(U)
2.0
15
GMV-ND48T/C-T(U)
2.0
15
(1) An all-pole disconnection switch having a contact separation of at least 3mm (1/8 inch) in all poles should be
connected in fixed wiring.
(2) The circuit breaker and power cord specification in above sheet is based on max power (max current) of the
unit.
(3) The power cord specification in above sheet is based on ambient temperature of 40°C(104°F).
(4) The circuit breaker specification in above sheet is based on ambient temperature of 40°C(104°F). If the
working condition is different, please adjust it according to the specification sheet of circuit breaker.
4 Installation Instructions
4.1 Installation of Indoor Unit
4.1.1Ceiling opening Dimension and suspension bolt position.
Fig.4.1.1
Unit: mm (inch)
Model
A
B
C
D
E
GMV-ND07~48T/C-T(U) 950(37 3/8)
890(35)
840(33 1/8)
680(26 3/4)
780(30 3/4)