Multi Variable Air Conditioners Indoor Unit for North America
96
3.11.3 Selection of air switch and power cord
Model
Power Supply
Circuit
Breaker
Capacity (A)
Minimum Sectional
Area of
Ground Wire
(mm
2
/AWG)
Minimum Sectional Area of
Power
Cord
(mm
2
/AWG)
GMV-ND24A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND30A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND36A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND42A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND48A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND54A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
3.12 Installation of AHU-KIT type Indoor Unit
3.12.1 Outline and installation dimension
Size of EXV box for GMV-N12U/A-T(U)
、
GMV-N24U/A-T(U)
、
GMV-N48U/A-T(U) and
GMV-N96U/A-T(U) (Unit: mm(in.)):
326 (12 7/
8)
203 (8)
85
(3 3/8)
150(6)
40
(1 4/7)
250 (9 7/
8)
174 (6 7/8)
200 (7 7/8)
290 (11 7/1
6)
4×Φ6
4×Φ12
Size of EXV box for GMV-N192U/A-T(U) (Unit: mm(in.)):