GMV DC Inverter VRF
7
2.2.2 Combinations of Indoor and Outdoor Units
(1) The following table indicates the number of IDU for ODU
:
ODU model
Max number of connectable
IDU (unit)
ODU model
Max number of connectable
IDU (unit)
GMV-224WM/H-X
13
GMV-1400WM/H-X
66
GMV-280WM/H-X
16
GMV-1455WM/H-X
69
GMV-335WM/H-X
19
GMV-1510WM/H-X
71
GMV-400WM/H-X
23
GMV-1565WM/H-X
74
GMV-450WM/H-X
26
GMV-1630WM/H-X
77
GMV-504WM/H-X
29
GMV-1680WM/H-X
80
GMV-560WM/H-X
33
GMV-1734WM/H-X
80
GMV-615WM/H-X
36
GMV-1790WM/H-X
80
GMV-680WM/H-X
39
GMV-1845WM/H-X
80
GMV-730WM/H-X
43
GMV-1905WM/H-X
80
GMV-784WM/H-X
46
GMV-1959WM/H-X
80
GMV-840WM/H-X
50
GMV-2015WM/H-X
80
GMV-895WM/H-X
53
GMV-2070WM/H-X
80
GMV-950WM/H-X
56
GMV-2125WM/H-X
80
GMV-1015WM/H-X
59
GMV-2180WM/H-X
80
GMV-1065WM/H-X
63
GMV-2245WM/H-X
80
GMV-1119WM/H-X
64
GMV-2295WM/H-X
80
GMV-1175WM/H-X
64
GMV-2349WM/H-X
80
GMV-1230WM/H-X
64
GMV-2405WM/H-X
80
GMV-1290WM/H-X
64
GMV-2460WM/H-X
80
GMV-1345WM/H-X
64
——
——
(2) The total capacity of indoor units should be within 50%~135% of that of outdoor units.
(3) When any one of the indoor units receives the operation command, the outdoor unit starts
running according to the required capability; when all indoor unit stops running, the outdoor
unit stops operation.