WARNING !

All installation and commissioning shall be performed by the qualified serviceman in accordance

with instructions covered in the manual, otherwise it would cause water leakage, electric shock 
or fire hazard etc.    

The unit shall be wired as per the wiring diagram, otherwise the electric motor would be burned

out.

The unit shall be grounded reliability to avoid hurt on the human body or damage on properly due

to poor insulation.        

Before obtaining access to terminals, all supply circuits must be disconnected.

User Notice

This appliance is intended to be used by expert or trained users in shops, in light industry and on 

farms, or for commercial use by lay persons.

DISPOSAL

: Do not dispose this product as unsorted municipal waste. Collection of 

such waste separately for special treatment is necessary.

This appliance can be used by children aged from 8 years and 

above and persons with reduced physical,  sensory or mental 

capabilities or lack of experience and knowledge if they have been 

given supervision or instruction concerning use of the appliance 

in a safe way and understand the hazards involved.Children shall 

not play with the appliance. Cleaning and user maintenance shall 

not be made by children without supervision.

1 APPLICATION SCOPE

(1) 

The entering water temperature for cooling shall not be lower than 5°C, otherwise it would 

cause sweating on the surface of the unit. The entering water temperature for heating shall not 
be higher than 80°C(60°C), otherwise it would corrode the copper tube .

(2) 

The range of the ambient temperature for cooling shall be 16-40°C and be 10-35°C for heating. 

The relative humidity shall be or less than 95%.

(3) The unit is categorized into the comfort air conditioning unit and shall not be installed where 

there is corrosive, inflammable gas or smog (like, kitchen) and wet (like, laundry), otherwise 
the unit would fail to operate properly and the service life would be shortened.

(4) The A-weighted sound pressure level is below 70dB.

2 INSTALLATION INSTRUCTIONS

(1) 

The unit shall be installed by the skilled servicemen who have well knowledge of this product 

and also the local laws and regulations.

(2) 

See the figures below for installation dimensions. (Unit: mm)

Slotted Hole

L

L

510

L+36

a

b

4-10×20

302

88

30

163.6

191

235

227

130

245

WA-K Series

L

a

b

WA-K Series

L

a

b

FP-34WA(H)-K

490

45

310

FP-102WA(H)-K

820

45

310

FP-51WA(H)-K

620

45

310

FP-136WA(H)-K

1400

75

250

FP-68WA(H)-K

740

45

310

FP-170WA(H)-K

1400

75

250

FP-85WA(H)-K

820

45

310

FP-204WA(H)-K

1400

75

250

WAS Series

L

a

b

WAS Series

L

a

b

FP-34WAS-R

490

45

310

FP-102WAS-R

980

45

310

FP-51WAS-R

620

45

310

FP-136WAS-R

1400

75

250

FP-68WAS-R

740

45

310

FP-170WAS-R

1500

75

310

FP-85WAS-R

820

45

310

FP-204WAS-R

1500

75

310

F-T Series

L

a

b

F-T Series

L

a

b

FP-34WAF(T)-R

490

45

310

FP-102WAF(T)-R

980

45

310

FP-51WAF(T)-R

620

45

310

FP-136WAF(T)-R

1400

75

250

FP-68WAF(T)-R

740

45

310

FP-170WAF(T)-R

1500

75

310

FP-85WAF(T)-R

820

45

310

FP-204WAF(T)-R

1500

75

310

a

b

Slotted Hole

4-10×20

220

L+36

L

115

350

340

287.

5

230

325

588

WAS Series

L

a

b

F-T Series

L

a

b

FP-238WAS-R

1250

68

284

FP-238WAF(T)-R

1250

68

284

FP-272WAS-R

1250

68

284

FP-272WAF(T)-R

1250

68

284

FP-306WAS-R

1500

68

284

FP-306WAF(T)-R

1500

68

284

FP-340WAS-R

1500

68

284

FP-340WAF(T)-R

1500

68

284

245

191

235

225

130

30

163.

6

88

310

L+36

45

L

476

302

Slotted Hole

4-10×20

WA-K Series

L

FP-51WA5S-K

620

FP-68WA5S-K

740

FP-102WA5S-K

820

(3) The unit shall be installed securely. When installing hanger bolts, be sure they are capable of 

withstanding 4 times the weight of the unit. If unsure, they shall be reinforced. The weight of 
the unit is specified on the nameplate. 

(4) Enough service space shall be left around the unit as shown in the figure below.

>0.3m

>0.25m

(5) 

The drain pan shall tilt toward the drain outlet with a desired downward slope. Hanger bolts are 

only intended to bear the weight of the unit other than the outside force of the duct, water pipe 
and others. 

(6) The length of the duct shall be compatible with the rated static pressure, otherwise the unit 

would fail to run properly. The inlet and outlet of the duct shall be attached with flexible 
connections.

(7) Water pipes shall be cleaned up prior to installation, and the outlet shall be equipped with a 

filter to prevent valves from being clogged by foreign matters.

(8) 

The unit shall be protected again dust during installation.

(9) 

A filter shall be installed at the return air inlet and be cleaned frequently to guarantee the 

expected heat exchange efficiency.

(10) 

The duct shall comply with requirements stated below.

1)

The duct shall be designed and installed as per the applicable local standards.

2) The duct shall be designed so that its sectional area won’t change suddenly and the air

direction won’t change at the outlet.

3) The duct shall be insulated reliably to prevent sweating under the cooling operation.

(11) 

Water pipes shall comply with requirements stated below.

(12) 

The drain pipe and inlet/outlet pipe shall be with the standard threaded pipe fittings. Water 

pipes shall be installed as per applicable local standards. During installation, do not over-
tighten the pipe fittings to avoid any damage on the header and connections of the coil.

1) The inlet/outlet pipe shall be installed in accordance with the applicable labels and equipped

with the quakeproof flexible connections and movable joints, as well as suitable filters
to prevent the heat exchanger from scaling which then would lower the heat exchange
efficiency.

2)

The inlet/outlet pipe shall be equipped with valves to control and cut off the water flow. The

weight of water pipes shall not be withstood by the main unit.

3) The inlet/outlet pipe, drain pipe and valves shall be insulated to prevent sweating under the

cooling operation in summer.

4) The condensate drain pipe should be installed downward with a slope larger than 5% to

facilitate drainage.

5)

Do not drag and pull water pipes forcibly and seal them with Teflon tape to avoid water

leakage.

(13) Be sure the power supply coincides with that specified on the nameplate and is cut off prior 

to electric installation. Electric wiring shall be performed in accordance with the electric wiring 
diagram as shown the figure below and the unit shall be grounded reliably. The appliance shall 
be installed in accordance with national wiring regulations.

(14) The power cord technical data we recommended is 0.5*3(Unit:mm

2

*ROT).

(15) 

If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or 

similarly qualified persons in order to avoid a hazard.

(16) Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring 

rules.

(17) 

The appliance is intended to be permanently connected to the water mains and not connected 

by a hose-set.

Concealed Ceiling Type Fan Coil Unit
Owner's Manual (Original Instructions)
Commercial Air Conditioners