3�4 Debugging of Cooling Mode
Step1: make sure that the compressor has been preheated for over 8 hours before first startup of it.
Step 2: Connect monitoring instrument of debugging.
Step 3: After the monitoring instrument has been installed, check if the communication of data is normal, if all indoor
units and wired controllers can be viewed on monitoring software and if there is any repeated code or wire dropped off.
When it is normal, the address of wired controller shall be corresponding to
address of indoor unit, which is shown as Fig. A.
Address of wired controller
Address of inddor unit
Fig.A