SHEVS Control Centre   RWZ  5 f 

 

 

 

 

3

 

1

 

Concept of Control Centre 

●  SHEVS Control Centre with four outputs for connecting 24 V actuators (RWZ 5f-xx) or 48 V actuators 

(RWZ 5f-xx-48V) 

●  Functions according to EN 12101-10 (power supply), ISO 21927-9 (control), VdS 2581 and VdS 2593 
●  Selectable group configuration: one or two SHE groups, up to four ventilation groups 
●  For every SHE group, two signal lines: 

−  Line 

T

: Automatic fire detectors or fire alarm control panel (FACP) 

−  Line 

t

: Manual call points 

RT 2

 or

 RT 4

 (main alarm point RT 2/4-*-BS or secondary alarm point 

RT 2/4-*). Connectable versions see section 6 “Technical Data” 

●  Line

 

Y

 for connecting a FACP (activating the alarm in both SHE groups) 

●  Reset the alarm / the detectors using the button in the main alarm point or in the Control Centre 
●  Selectable functions: 

−  “Auto Close” (automatic closure after resetting an alarm) 
−  “Fault = Alarm” (fault in a signal line will trigger an alarm) 
−  “Automatic OFF” (automatic travel commands - apart from the alarm - are disabled) 
−  “Thermal Alarm” (alarm on exceeding an enclosure inside temperature of 70 °C) 
−  “2-detector-dependency” (2-detector dependency for automatic fire detector in line 

T

−  “WRC” (automatic closure in the case of active wind and rain control) 

●  Possibility of connecting ventilation button for each ventilation group, also with indication of position 

A

 

●  For each actuator output adjustable ventilation position 

h

 and ventilation time 

D

 

●  Possibility of connecting an external wind and rain control, e.g., type 

WRS

. Internal wind and rain control, op-

tional 

●  Internal service display for indicating the detailed status 
●  The use of K + G / Grasl actuators is recommended. When controlling 3rd party actuators, compatibility is to 

be checked. Also note section 6 „Technical Data“ for this 

●  Connectable actuators: 24 V / 48 V actuators, travelling time for full stroke at rated load (total travelling time)  

< 4 minutes 

●  When directly changing the sense of travel, the actuators are stopped briefly before change of sense 
●  Sheet steel enclosure, light grey (RAL 7035) 

 

1.1

 

Options / Accessories 

● 

PK:

 Potential-free contacts (PFC) for alarm and/or fault forwarding 

● 

PK-SA:

 Potential-free contacts for forwarding indication of position 

● 

WTM:

 Outputs for controlling external warning devices in case of alarm or fault 

● 

WRM:

 Internal wind and rain control. Connection of wind sensor 

WM

 and/or rain sensor 

RS

 is required (ac-

cessory) 

i

  The PK-SA and WTM options cannot be provided at the same time! 

 

2

 

Putting into service / Putting out of service 

Work may be performed only by qualified personnel! 
Before starting any work, it is mandatory to deflect static charge! 

We do not assume any guarantee or liability for defects caused by faulty connection. 

i

 

Planning and design of SHEVS require observation of the following rules, as far as applicable: National build-
ing codes/model building code and regulations of local building and fire safety authorities, VDE regulations 
(particularly VDE 0100, 0108 and 0833), VdS Guidelines 2098 and 2221, DIN 18232, EN 12101, DIN 4102, 
model line systems policy. 
 

2.1

 

Installation / Putting into service 

!

 

Perform work only in de-energised condition! 

!

  Actuators must not be actuated directly (e.g., with external accumulators during installation / maintenance) 

when they are already connected. This can lead to defects in the power output. 

●  Fasten the enclosure securely to a wall using suitable mounting material. Guide the connection cables 

through the openings provided and wire them according to the connection diagrams. 

●  Make function settings (see 3.2). 
 

 

Summary of Contents for RWZ 5 f

Page 1: ...w kg pneumatik de GRASL Pneumatic Mechanik GmbH Europastra e 1 3454 Reidling sterreich Austria 43 0 22 76 21 200 0 43 0 22 76 21 200 99 _ Office graslrwa at www graslrwa at Smoke and Heat Ventilation...

Page 2: ...ice Putting out of service 3 2 1 Installation Putting into service 3 2 2 Putting out of service 4 3 Functions and operation 4 3 1 Indicators control elements of the Control Centre 4 3 2 Group configur...

Page 3: ...rty actuators compatibility is to be checked Also note section 6 Technical Data for this Connectable actuators 24 V 48 V actuators travelling time for full stroke at rated load total travelling time 4...

Page 4: ...2 Putting out of service Disconnect the accumulators from the Control Centre remove accumulator connection line or fuses F2 1 and F2 2 i Charged accumulators have a shelf life of about 6 months They...

Page 5: ...vated The indicators r on the logic board and the manual call points flash manual call points with buzzer S emit an intermittent warning tone After changing the switch position a recalibration is perf...

Page 6: ...with a key Automatic fire detectors The alarm is triggered automatically depending on the type of detector due to smoke and or heat detection If an automatic fire detector responds immediately after...

Page 7: ...hen activating the programming mode then the actuators of the related output are not fully retracted and the ventilation position cannot be set By pressing the button h closing can be activated for th...

Page 8: ...or 9 flashes after about 11 months of ser vice life After about 14 months the overdue maintenance leads to the indication of a fault s Accumulators Check the accumulators at least once a year for prop...

Page 9: ...d off again after 10 s in the event of a power failure In this case it can be switched on again for 10 s by pressing the button Reset S for 4 s Operating conditions Code Description Code Description 0...

Page 10: ...penings from behind W 430 x H 525 x D 185 13 x M16 1 x M20 8 x M25 144 x 34 mm W x H Environmental class 1 EN 12101 10 ISO 21927 9 III VdS 2581 Relative humidity Enclosure protection rating 5 C 40 C 2...

Page 11: ...10 0 mm 290 m 145 m 97 m 73 m 58 m 48 m 41 m 36 m When 4 cores are used connect 2 cores each in parallel Actuator outputs 48V types RWZ 5f xx 48V Rated voltage Operating mode duty cycle Maximum cross...

Page 12: ...f cable max 400 m if not specified otherwise Run the supply line unbranched to under the roof For permissible cable length see section Technical Data When using 4 cores 2 cores each in parallel greate...

Page 13: ...bu 10 9 8 7 6 5 10 9 8 7 6 5 Line RT 4 BS RT 2 see page A 5 RT 4 see page A 6 Example of connection Mains Actuators Line Line Colour code for resistors 10k brown black black red 1k5 brown green black...

Page 14: ...tored common line Colour code for resistors 10k brown black black red Actuators must not be actuated directly e g with external accumulators during installation maintenance when they are already conne...

Page 15: ...anel FACP Fire Alarm Control Panel FACP Colour code for resistors 10k brown black black red 1k5 brown green black brown Line Line FACP NO contact FACP NC contact Normally open contact Normally closed...

Page 16: ...S s o r r 1st SHE group X4 1 Smoke Exhaust o s r Reset r Reset S S RT 2 BS AA 21 19 22 20 1 3 5 2 4 6 7 9 11 8 10 12 Smoke Exhaust o s r Reset r RT 2 BS 1 3 5 2 4 6 7 9 11 8 10 12 Line Colour code fo...

Page 17: ...Reset r Reset o s r H r Reset S S Smoke Exhaust 10 9 8 7 6 5 10 9 8 7 6 5 10 9 8 7 6 5 10 9 8 7 6 5 10 9 8 7 6 5 10 9 8 7 6 5 7 6 5 7 6 5 14 13 14 13 Smoke Exhaust o s r H Reset r r H Smoke Exhaust Li...

Page 18: ...ernal Wind and Rain Control 1st ventilation group 2nd ventilation group The connection is made as shown for the 1st group but using terminal strip X2 2 Use a separate contact for each connected Contro...

Page 19: ...ccu rd bu bk rd bu bk 12 V Accu 12 Ah 12 Ah Line voltage Installation Accumulators Insert the accumulators in the enclosure as illustrated and connect them When putting into out of service observe the...

Page 20: ...ODUP GHWHFWRU GHSHQGHQF XWRPDWLF 2 3 VZLWFK IRU HDFK YHQWLODWLRQ JURXS 3 VZLWFK IRU HDFK DFWXDWRU RXWSXW XWR ORVH 5 XVHV 0DLQV SULPDU FFXPXODWRUV FWXDWRUV FWXDWRUV 3 VZLWFK R QRW FKDQJH WKH VHWWLQJ D...

Reviews: