
Combi 90 Outdoor Module
12
Fig. 6
1
The pipework connections are housed within an
insulated compartment inside the rear end of the
boiler casing (opposite end from the burner). These
connections are accessed by removing the back panel
of the enclosure.
2
The boiler side panels are fitted with movable plates
to allow the pipework to exit the boiler enclosure. The
side flue exit holes in the side panels may also be
used to route the pipework and cables into the
building. Where the boiler is sited remotely from the
building, the pipework can be routed through the
holes in the base of the rear compartment.
Water connections
4.4
6
The filling loop kit and pressure gauge supplied,
should be located in a convenient and easily
accessible position inside the house, where the gauge
will be visible to the User (see Fig. 7).
Fit the double check valve to the mains water supply,
ensuring correct flow direction as indicated by the
arrow on the valve. Fit the pressure gauge and shut-
off valve to the central heating system. Fit the flexible
filling hose between the two valves.
Fig. 7
4 - BOILER INSTALLATION
3
The cold mains and domestic hot water connections are
supplied with 15 mm Tectite elbows which can be turned
to allow either left or right hand pipe entry. It is
recommended that an isolating valve be fitted on the
cold mains supply pipe at a point where the supply leaves
the building and before it enters the Module casing.
4
The heating flow should be fitted with the 22 mm
Tectite elbow supplied to allow either left or right
hand pipe entry.
5
The boiler is fitted with a 1" BSP heating return tapping
mounted centrally at low level on the rear of the water
jacket. A 1" BSP x 22 mm bent coupling is supplied.