Grand Aire WATPM Series Installation Instructions Manual Download Page 10

10

7. REFRIGERANT CONNECTIONS

Keep the coil connections sealed until refrigerant connections are 
made. See the Installation Instructions for the outdoor unit for details 
on line sizing, tubing installation, and charging information.
Coil is shipped with “N2”. Evacuate the system before charging with 
refrigerant.
Install refrigerant tubing so that it does not block service access to 
the front of the unit.
Nitrogen should flow through the refrigerant lines while brazing.
Use a wet rag or an approved heat paste to protect the TXV sensing 
bulb during the braze process.
 After the refrigerant connections are made, seal the gap around the 
connections with pressure sensitive gasket.  

Do not, under any circumstances, connect return ductwork to any 
other heat producing device such as fireplace insert, stove, etc. 
Unauthorized  use  of  such  devices  may  result  in  fire,  carbon 
monoxide  poisoning,  explosion,  personal  injury  or  property 
damage.

Sheet metal ductwork run in unconditioned spaces must be insulated 
and covered with a vapor barrier. Fibrous ductwork may be used if 
constructed and installed in accordance with SMACNA Construction 
Standard  on  Fibrous  Glass  Ducts.  Ductwork  must  comply  with 
National Fire Protection Association as tested by U/L Standard 181 
for Class I Air Ducts. Check local codes for requirements on ductwork 
and insulation.

Duct system must be designed within the range of external static 
pressure the unit is designed to operate against. It is important 
that the system airflow be adequate. Make sure supply and return 
ductwork, grills, special filters, accessories, etc. are accounted for 
in total resistance. See airflow performance tables in this manual. 

Design the duct system in accordance with “ACCA” Manual “D” 
Design for Residential Winter and Summer Air Conditioning and 
Equipment Selection. Latest editions are available from: “ACCA” 
Air Conditioning Contractors of America, 1513 16th Street, N.W., 
Washington, D.C. 20036. If duct system incorporates flexible air 
duct, be sure pressure drop Information (straight length plus all 
turns) shown in “ACCA” Manual “D” is accounted for in system. 

Supply plenum is attached to the 3/4” duct flanges supplied with 
the unit. Attach flanges around the blower outlet.
IMPORTANT: If an elbow is included in the plenum close to the 
unit, it must not be smaller than the dimensions of the supply duct 
flange on the unit.

 IMPORTANT: The front flange on the return duct if connected to 
the blower casing must not be screwed into the area where the 
power wiring is located. Drills or sharp screw points can damage 
insulation on wires located inside unit.

Secure the supply and return ductwork to the unit flanges, using 
proper fasteners for the type of duct used and tape the duct-to-
unit joint as required to prevent air leaks. 

WARNING

The air distribution system has the greatest effect on airflow. The duct 
system  is  totally  controlled  by  the  contractor.  For  this  reason,  the 
contractor should use only industry-recognized procedures.
Heat pump systems require a specified airflow. Each ton of cooling 
requires between 350 and 450 cubic feet of air per minute (CFM), or 
400 CFM nominally.
Duct  design  and  construction  should  be  carefully  done.  System 
performance  can  be  lowered  dramatically  through  bad  planning  or 
workmanship.
Air supply diffusers must be selected and located carefully. They must 
be sized and positoined to deliver treated air along the perimerter of 
the space. If they are too small for their intended airflow, they 
become noisy. If they are not located properly, they cause drafts. 
Retur

n

 air grilles must be properly sized to carry air back to the 

blower.

 

If they are too small, they also cause noise.

The  installers  should  balance  the  air  distribution  system  to  ensure 
proper quiet airflow to all rooms in the home. This ensures a comfort-
able living space.
An air velocity meter or airflow hood can be used to balance and verify 
branch and system airflow (CFM). 

6. DUCTWORK

Field  ductwork  must  comply  with  the  National  Fire  Protection 
Association  NFPA  90A,  NFPA  90B  and  any  applicable  local 
ordinance.

Summary of Contents for WATPM Series

Page 1: ...e instruction may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock property damage personal injury or death 1 SAFETY 2 2 GENERAL 3 3 APPLICATIONS 5 4 ELECTRICAL WIRING 7 5 AIRFLOW PERFORMANCE 9 6 DUCTWORK 10 7 REFRIGERANT CONNECTIONS 10 8 AIR FILTER not factory installed 11 9 FILTER INSTALLATION DIMENSIONS 12 10 WIRING 13 PARTS LIMITED W...

Page 2: ...e possibly resulting in fire electrical shock property damage personal injury or death The unit must be permanently grounded Failure to do so can result in electrical shock causing personal injury or death WARNING PROPOSITION 65 This appliance contains fiberglass insula tion Respirable particles of fiberglass are known to State of California to cause cancer All manufacturer products meet current f...

Page 3: ... slab with supply air plenum and ductwork completely encased must be not less than 2 inches of concrete See NFPA 90A The unit can be positioned for upflow left and right downflow position This Air Handler provides the flexibility for installation in any upflow or downflow horizontal application The direct drive motors provides a selection of air volume to match any application 5 Speed motors provi...

Page 4: ...05 16 NOTE 25 CLEARANCE IS REQUIRED IN THE FRONT OF THE UNIT FOR FILTER AND COIL MAINTENANCE SUPPLY AIR FLANGES ARE PROVIDED FOR FIELD INSTALLATION ELECTRICAL CONNECTIOS MAY EXIT TOP OR EITHER SIDE HIGH VOLTAGE CONNECTION 7 8 1 3 8 1 3 4 DIA KNOCK OUTS LOW VOLTAGE CONNECTION BREAKER SWITCH FOR ELECTRIC HEATER ONLY VAPOR LINE CONNECTION COPPER SWEAT LIQUID LINE CONNECTION COPPER SWEAT AUXILIARY DRA...

Page 5: ... mounting tab over edge in opening With screwdriver or pencil pull blue tab with hole away from breaker while setting that side of breaker into opening When breaker is in place release tab locking circuit breaker into location in opening Repeat above operation for remaining breaker s if more than one is provided Replace single point wiring jumper bar if it is used on line side of breaker and tight...

Page 6: ...PLICATIONS lower front service panel removed view AIRFLOW AIRFLOW Fig 4 INDOOR COIL AND DRAIN PAN SET UP HORIZONTAL ADAPTER KIT VAPOR LINE CONNECTION LIQUID LINE CONNECTION TXV PRIMARY DRAIN CONNECTION VERTICAL DRAIN PAN AUXILIARY HORIZONTAL AUXILIARY UPFLOW DOWNFLOW STRAPS REAR WATER CATCHER TOP AIR STOP DRAIN CONNECTION DRAIN CONNECTION ...

Page 7: ...d power wiring has been maintained Grounding may be accomplished by grounding metal conduit when installed in accordance with electrical codes to the unit cabinet Grounding may also be accomplished by attaching ground wire s to ground lug s provided in the unit wiring compartment Use of multiple supply circuits require grounding of each circuit to lug s provided in unit Horizontal units must be co...

Page 8: ...e 29 7 26 2 42 7 37 5 55 8 48 8 33 6 30 1 35 46 6 41 4 50 45 59 6 52 7 60 60 240 208 240 208 X X X X X X X X X X X X X X X X X X X X X X X X X 5 28 5 24 9 30 25 7 5 41 5 36 3 45 40 10 54 5 47 6 60 50 5 30 30 7 5 45 40 10 60 50 5 7 5 10 15 20 15 60 24 36 MIN Circuit Ampacity MAX Fuse or Breaker HACR Ampacity Heat Kit Model Air Handler Model kW Electric Heat 5 7 5 10 15 20 48 Fan speed 1 2 3 4 5 X 5...

Page 9: ... 64 72 1532 1471 1428 1386 1372 1327 1271 1210 1159 1101 233 247 262 266 270 275 281 290 298 310 1408 1343 1297 1265 1246 1197 1141 1073 1015 880 197 209 214 219 222 227 238 245 256 273 1326 1230 1174 1151 1107 1024 896 828 807 726 148 165 172 175 183 190 202 217 221 225 1236 1175 1100 1075 1029 963 835 736 661 582 124 130 133 137 142 146 157 168 176 187 1182 1141 1020 995 944 818 648 553 461 363 ...

Page 10: ...D C 20036 If duct system incorporates flexible air duct be sure pressure drop Information straight length plus all turns shown in ACCA Manual D is accounted for in system Supply plenum is attached to the 3 4 duct flanges supplied with the unit Attach flanges around the blower outlet IMPORTANT If an elbow is included in the plenum close to the unit it must not be smaller than the dimensions of the ...

Page 11: ...ure installation of these such filtration systems are installed correctly IMPORTANT DO NOT DOUBLE FILTER THE RETURN AIR DUCT SYSTEM DO NOT FILTER THE SUPPLY AIR DUCT SYSTEM THIS WILL CHANGE THE PERFORMANCE OF THE UNIT AND REDUCE AIRFLOW 7 1 CONDENSATE DRAIN TUBING Consult local codes for specific requirements IMPORTANT 1 When making drain fitting connections to the drain pan use a thin layer of Te...

Page 12: ...direction as airflow 9 FILTER INSTALLATION DIMENSIONS Fig 6 EXTERNAL FILTER BASE DIMENSIONAL DATA 24 18Χ20 457Χ508 18 3 466 21 6 548 1 25 4 20 8 16 3 36 48 60 20Χ22 508Χ559 20 7 526 23 9 608 1 25 4 23 18 8 H IN mm Return width A IN Return length B IN MODEL FILTER SIZE IN mm W IN mm D IN mm H W B RETURN AIR OPENING DEPTH A D FILTER RAILS FILTER COVER MANUAL BOLT NOTE Air filter is optional part not...

Page 13: ...ns H P system with electric heating Wiring please refer to the Owner s Manual of the thermostat W2 D w1 These units must be wired and installed in accordance with all National and Local Safety Codes 24 48 60 Phase Voltage frequency Input Current Fuse Indoor unit A 15A 15A 15A 15A Line Quantity 3 3 3 3 Line Diameter AWG 14 14 14 14 Line Quantity 3 3 3 3 Line Diameter AWG 14 12 10 10 Line Quantity 4...

Page 14: ...nit 2 To Be Wired In Accordance With NEC And Local Codes 3 If Any Of The Original Wire As Supplied Must Be Replaced Use The Same Or Equivalent Type Wire 4 Connect R To R G To G Etc See Outdoor Instruction For Details 5 To Change Speed Tap Regulation of SW1 to choose the Speed 6 See Airflow Tables For Tap Usage 5 4 3 2 1 CN6 BROWN CN1 CN2 PLUG LIATE BLACK C W321 ON 123 SW1 ON 123 ON 123 SW1 ON 123 ...

Page 15: ... 6 6 7 1 0 6 7 1 0 1 2 5 1 2 3 4 5 6 7 5kW HEAT KIT HEATER KIT PLUG 7 5kW CB1 50A 10kW CB1 60A 4 8 2 6 2 4 8 2 6 5 8 2 4 5 5 5 7 8 5 7 6 7 0 6 1 6 8 5 5 7 8 5 7 6 7 0 6 1 6 8 E T I H W 2 5 8 2 W L1Ć L2Ć L1 L2 6 6 7 1 0 4 8 2 6 5 5 5 8 8 1 W 7 L1Ć L2Ć L1 L2 E U L B D E R 6 6 6 7 1 0 6 7 1 0 1 2 5 1 2 3 4 5 6 15kW HEAT KIT 10kW 5kW HEATER KIT PLUG 4 8 2 6 2 4 8 2 6 5 2 5 5 5 7 8 5 7 6 7 0 6 1 6 8 E ...

Page 16: ...2020001C1079 V1 2 ...

Reviews: