Wallbox Input Closure Interface
GRX-WCI

PELV (Class 2: USA) Devices
GRAFIK Eye 
3000 12 V

200 mA

GRAFIK Eye 4000 24 V

100 mA

R

Chinese

English

Español

Français

Português

Nederlands

Deutsch

Italiano

Overview

The GRX-WCI is for use
with 

GRAFIK Eye

3000

and 4000 series systems.
The GRX-WCI mounts
behind the user-supplied
switch to select or adjust
scenes in up to eight
control units. The
interface provides from
two to seven contact
closure inputs.

Specifications

• Operating voltage: PELV (Class 2: USA) low-voltage

type inputs, 12 V

when used on a GRX-3000 system

and 24 V

when used on a GRX-4000 system.

• If input switch is solid state, it must have an output with

an on-state saturation voltage less than 1 V

at 1 mA

and an off-state leakage current of less than 1 mA.
Outputs must be capable of switching operating
voltage for desired life of system.

• The recommended wallbox depth is 61 mm. The

wallbox depth requirements vary with the depth of the
switch being used.

• The GRX-WCI uses one address on the communication

link.

• If there is any question as to whether a switch is

compatible with these specifications, contact the
manufacturer of the switch.

Environment:

Ambient operating temperature 0-40 °C

(32-104 °F), 0-90% humidity, non-condensing. 

Indoor

use only.

Caution:

The GRX-WCI is 

not

designed to work

with the line/mains voltage switches. Use with
line/mains voltage switches could result in
premature failure of the switch being used.

Caution:

Install in accordance with all local and

national electric codes. 

Low-Voltage PELV (Class 2: USA) Wiring

• Use low-voltage PELV (Class 2: USA) wiring to daisy-

chain the GRX-WCI to GRX-3000/4000 control units
and other components.

• Make connections inside the wallbox, switchbox, or

junction box with a maximum wire length of 2.5 m 
from the link to the GRX-WCI.

When used with GRX-3000 control units:

• Use two 1.0 mm

2

(#18 AWG) conductors for common

(terminal 1) and 12 V

(terminal 2). Be sure to wire the

terminal 2 connection correctly; refer to the GRX-3000

Installation Guide

.

• Use one shielded, twisted pair 1.0 mm

2

(#18 AWG)

wires for data link (terminals 3 and 4).

When used with GRX-4000 control units:

• Use two 2.5 mm

2

(#12 AWG) conductors for common

(terminal 1) and 24 V

(terminal 2). These will not fit

into terminals; see next page for connection details.

• Use one shielded, twisted pair 1.0 mm

2

(#18 AWG)

wires for data link (terminals 3 and 4).

• Connect drain/shield as shown on next page.

-Do not connect ground/earth to GRX-WCI.

-Connect the bare drain wires and cut off the outside

shield.

Installation Instructions
Please Read before Installing

Input wiring
harness

Program
button

Addressing
and function
switches

Power
LED