Screen Identification
332078C
33
This indicates that the unit could not fill its plungers completely. Verify the following:
•
Verify the feed system is functioning and providing enough pressure. If installed, refer to the SR657-1M-LR
Meter-Mix Dispense Systems-Operation manual for additional details.
•
The A-B Minimum Refill Pressure on Preset Screen 2 is reasonable.
•
Air Pressure To Cylinder on Preset Screen 2 may need to be increased.
•
The Refill Fault Timer on Preset Screen 2 may need to be increased.
This indicates that the feed unit could not provide enough pressure during refill.
•
Verify that it is functioning properly and is providing enough pressure to the unit. If installed, refer to the
SR657-1M-LR Meter-Mix Dispense Systems-Operation manual for additional details.
•
Verify that a reasonable Packing Pressure has been selected on Preset Screen 1.
•
Verify the Refill Fault Timer on Preset Screen 2 provides enough time for refill. Refer to