Repair
30
3A8501A
Replace Circuit Breaker
on page 22.
2. Use an ohmmeter to check continuity across the
circuit breaker (top to bottom). If there is no
continuity, trip the breaker, then reset and retest it.
If there is still no continuity, replace the breaker:
a. Refer to the circuit breaker table in
on page 69.
b. Turn the main power switch (MP) off.
c. Loosen the two screws connecting the wires
and bus bar to the circuit breaker that will be
replaced, then disconnect the wires.
d. Pull the locking tab out 1/4 in. (6 mm) and pull
the circuit breaker away from the din rail. Install
the new circuit breaker. Insert the wires and
tighten down all screws.
WLD
MP
Circuit Breakers
Ref. Size Component
CB1 40A
A (ISO) Heat
CB2 40A
B (RES) Heat
CB3 40A
Hose Transformer Primary
CB4 50A
Hose Heat
CB5 20A
Motor
ti41006a