Setup
3A7031A
15
Program Settings
Feature
Description
Modes of Operation Maximum/Minimum
and Additional Comments
Mode
Timer Machine Count
Machine Count
1 to 10,000
Machine Count Options
-
Action to start lubrication or alarm when timeout
expires
-
Enable a backup timeout
Interval
HH:MM (00:01 to 99:59)
Defines time between lubrication events
Mode
Timer, Pressure Switch, Pressure Sensor, Cycle
Timeout
HH:MM:SS (00:00:10 to 03:00:00)
Pressure Type
0-5V, 0-10V, 1-5V, 4-20mA
Pressure Sensor Units
PSI, kPa, bar, %
Pressure Sensor Full Scale
1 to 20,000
Requires: Threshold is less than or equal to Full Scale
Pressure Sensor Threshold
1 to 20,000
Requires: Threshold is less than or equal to Full Scale
Pressure Sensor Target
1 to 20,000
Requires: Threshold is less than or equal to Full Scale
Cycles
0 to 100
Cycle Option Solenoid Alarm
Enables alarm when cycles are detected during idle time
, page 13
Low Level Type
Paddle, Low Level Switch, Low Level Sensor
Paddle Low Level Alert
Threshold
Recommended: 10
00 to 99
Requires Alarm > Alert
Setting of zero disables low level alert threshold
Paddle Low Level Alarm
Threshold
Recommend: 80
00 to 99
Requires: Alarm > Alert
Setting of zero disables low level alarm threshold
Paddle Alarm Auto-Clear
Enables a feature that will automatically clear a low level
alarm and start a lubrication event to check if the reservoir is
still empty
Level Switch Type
Sets low level behavior as low level Alert or low level alarm
Sensor Type
0-5V, 0-10V, 1-5V, 4-20mA
Sensor Alert Threshold
0 - 100
Requires: Alarm < Alert
Setting of zero disables low level alert threshold
Sensor Alarm Threshold
0 - 100
Requires: Alarm < Alert
Setting of zero disables low level alarm threshold
Delay Time
MM:SS (00:01 to 59:59)
, page 14
Output Type
Activated pm Alarm, only, Alert only, Alarm and Alerts, or to
close Vent Valve
Date
Month: 1 - 12
Day: 1 - 31
Year: 18 - 99
Time
00:00:00 to 23:59:59
24-hour time