Troubleshooting
Error
Code
Error
Position
Type
Name
Cause
Solution
Bad Connection between
MCM (Port 2) and load
center board.
Check connection and
cables.
WMCE MCM
ALARM
Load Center Fault
Bad load center.
Replace load center. See
System Repair manual.
WSCX ADM
ADVISORY Invalid CAN
Configuration
Duplicate node on CAN
network.
Verify LPTCM are set to A
and B.
A valid configuration file
can't be found for the
USB.
Insert a system token into
the ADM and cycle the
power. Wait until the lights
on USB port stop flashing
before Removing the token.
WSUX USB
ADVISORY USB Invalid
Configuration
Bad ADM.
Replace ADM. See System
Repair manual.
WXUD ADM
ADVISORY USB Download
Error
Log Download Failed.
Backup and reformat the
USB drive. Retry download.
WXUU ADM
ADVISORY USB Upload Error Custom language file
failed to upload
Perform normal USB
download and use the new
disptext.txt file to upload the
custom language.
WX00 MCM
ALARM
External Input
The alarm external input
has been driven low.
An active alarm is being
generated by the external
trigger. If the external alarm
is not configured check for a
short in the wiring going to
MCM port 7, pins 1 and 3.
3A1705E
85
Summary of Contents for 259079
Page 34: ...Setup A5 A1 A2 AS AN A3 AT A3 A4 A2 A6 A4 34 3A1705E...
Page 45: ...Advanced Display Module ADM Operation Setup Screens Navigation Diagram Figure 35 3A1705E 45...
Page 49: ...Advanced Display Module ADM Operation Run Screens Navigation Diagram Figure 36 3A1705E 49...
Page 93: ...Dimensions Dimensions Top View Figure 43 Side View Figure 44 3A1705E 93...
Page 95: ...Dimensions Pallet Mounting Dimensions Figure 48 3A1705E 95...
Page 97: ...Notes Notes 3A1705E 97...