Grace PESDs CHEKVOLT R-3MT-VI Installation Manual & Operating Instructions Download Page 1

®

CHEKVOLT

®

 (R-3MT-VI)

 

INSTALLATION GUIDE & OPERATING INSTRUCTIONS

Grace Technologies, Inc.

 • 1515 E Kimberly Road • Davenport, Iowa 52807

Phone: 

1-800-280-9517 •  

Fax:

 (563)386-9639 • www.pesd.com

For technical questions call 1-800-280-9517 and select Option 3 for Technical Support when prompted

Non-Hazardous Locations

Indoor

Indoor/Outdoor

Ingress Protection

UL Type 12, 13

UL Type 4, 4X

IP66, IP69 per IEC 60529

Approvals

CSA C22.2 No. 94.2/ UL 50E

UL 61010-1 3rd Ed. with AMD 1

CAT III 1000V

CAT IV 600V

CE

UL/CSA 61010-2-030 2nd Ed.

EN 61010-2-030 2nd Ed.

Summary of Contents for PESDs CHEKVOLT R-3MT-VI

Page 1: ...w pesd com For technical questions call 1 800 280 9517 and select Option 3 for Technical Support when prompted Non Hazardous Locations Indoor Indoor Outdoor Ingress Protection UL Type 12 13 UL Type 4 4X IP66 IP69 per IEC 60529 Approvals CSA C22 2 No 94 2 UL 50E UL 61010 1 3rd Ed with AMD 1 CAT III 1000V CAT IV 600V CE UL CSA 61010 2 030 2nd Ed EN 61010 2 030 2nd Ed ...

Page 2: ... encapsulated between each input wire and respective test point 164KΩ 6W equivalent between any two test points Output Accuracy 3 2 of applied voltage with 10M Ω input impedance voltmeter connected to any 2 test points Terminations 4 Wires 8 ft 14 AWG 90 C 1000V UL 1452 PVC Insulated w Nylon Jacket Voltage Category Ratings CAT III 1000V Max Pollution Degree 3 CAT IV 600 V Max pollution Degree 3 Ho...

Page 3: ...V or 1000V with a momentary short between any 2 test points Do not operate above 1000V or 1000V 55 C ambient or 2000m altitude or 80 RH If this product is used in a manner not herein prescribed the protection provided may be impaired Use of an Overcurrent Protection Device or Fuse is NOT RECOMMENDED when installing these devices in safety applications for verifying both voltage presence and voltag...

Page 4: ...r disconnect side of the 3 Phase line voltage The Green Yellow stripe Grn Yel wire MUST be connected to Earth Ground Fig 2 4 With the R 3MT VI installed wired and the enclosure closed verify the power disconnect is OFF 5 Using the proper test equipment the voltmeter should be rated for Cat III 1000V and Cat IV 1000V Test probes should be fully insulated with 080 DIA points to insert into test poin...

Page 5: ...0 480 600 750 1000 Flashes Sec typical 0 1 1 5 3 3 9 4 5 4 6 4 8 4 9 1 Line to Line VAC 18 20 30 120 240 480 600 750 1000 Flashes Sec Typical 0 0 8 1 2 2 6 3 6 4 2 4 6 4 8 5 or Stored Energy DC 16 20 30 48 110 300 600 1000 Flashes Sec Typical 0 1 3 1 8 2 3 3 2 4 5 4 8 4 9 ...

Page 6: ...ed with the use and limitations of these devices and properly update the Point of Connections on your installation drawings MAINTENANCE With power removed free dust and particles from the front of the label and dust cap with compressed air Open the dust cap by unscrewing the cap screw and free the dust and particles on the inside of the cap and jack sockets with compressed air Maintain a clean lab...

Page 7: ...000V AC or DC CAT III is for circuits which can be connected to the mains installation of a building Energy is limited by circuit breakers to less than 110 000VA with the current not exceeding 11 000A CAT IV includes circuits which are connected directly to the source of power for a given building There are very high levels of available energy e g limited only by the power transformer and arc flas...

Page 8: ...LH Flange Label R 3MT VI LF Both the Horizonal and Flange labels are included in your kit Use the appropraite label per your installation requirements Custom labels are available upon request Please call 1 800 280 9517 or visit www pesd com Included in R 3MT VI KIT ...

Page 9: ...oprié en suivant la procédure adéquate selon les normes de la NFPA National Fire ProtectionAssociation 70E 120 1 5 120 2 F 2 f 1 6 de l OSHA Occupational Safety and HealthAdministration 1910 333 b 2 iv B THREE PHASE DELTA 3W GND TYPICAL CONFIGURATION WIRE IDENTIFICATION NOTE 4 Test point jacks accept 080 DIA probe points L1 L2 L3 Note 4 Test point jacks accept 080 DIA probe points Figure 1 Figure ...

Page 10: ... Figure 3 ...

Page 11: ... Fig 3 Fig 4 Figure 4 Figure 5 ...

Page 12: ...SS R3MTVI IG EN 2211 ...