Grace Industries MS2000X Series User Information Download Page 3

Page 3

MS2000X-H UI 0318

Terminal Block Labeling and Confi guration

Inside View of MS2000X with -AC, -B, -LS, and -D Options Installed

State of Inputs

Upgrade Port

Con

fi

 guration Port

A. 

Inputs and Power

Terminal rated for solid or stranded 

wire from 20-24AWG. Wire should 

be stripped at a 5/16”.

Red LED Indicates 

Relay is Active

C. 

Relay Terminals

Terminal rated for solid or stranded 

wire from 14-22AWG. Wire should 

be stripped at a 3/8”.

B. 

Power Terminals

Terminal rated for solid or stranded 

wire from 14-22AWG. Wire should 

be stripped at a 1/2”.

Additional Notes: 

 

•  Except for the battery, all parts of the MS2000X are attached to the PCB.

 

•  Connect the AC Power cable to the Line, Neutral, and Ground positions.

 

•  When setting case lid in place, make sure the light siren cable is NOT pinched.

To seal from intrusion of contaminants, secure the case lid by tightening all four (4) lid 
bolts until snug. 

 

•  Once Installation and Field Testing is complete, the MS2000X is ready for use. 

A.  Inputs and Power:

1-  15VDC – In

 

2-  +12VDC – Out

 3- 

GND

 4- 

GND

 5- 

INPUT#1

 6- 

Input 

Common

 7- 

INPUT#2

 8- 

Input 

Common

 9- 

INPUT#3

 10- 

Input 

Common

 11- 

INPUT#4

 12- 

Input 

Common

B. Power Terminals:

Line

 Neutral
 GND

C. Relay Terminals: 

(4 Sets; Numbered 1 - 4)

Normally Open 

 Common
 Normally 

Closed

MS2000X Factory Default Relay Setting

  Relay # 

Trigger 

Hold/Activation Time*

 

User Alarm or Input #1 Active (Transmit Alarm) 

20 Seconds 

 

Global Evac or Input #2 Active (Transmit Global Evac) 

20 Seconds 

 

Input #3 Active (Transmit Canned Message) ** 

3 Seconds 

 

Loss of AC Detected 

3 Seconds 

* Hold/Activation Time: How long relay contact will be maintained after last trigger 
message is received. 

** Canned and Free Form Messages will only be displayed on SC500 Product Line

MS2000X Factory Default Input Setting

  Input # 

Trigger 

Repeat Time

 1 

Transmit 

Alarm 

Seconds 

 

Transmit Global Evac 

6 Seconds 

 

Transmit Canned Message (Message#) ** 

1 Hour 

 

Transmit Free Form Message (“Input#4-MS2000”) ** 

1 Hour 

  Loss of AC 

Transmit Free Form Message (“AC LOSS-MS2000”) ** 

1 Hour 

 Low Battery 

Transmit Free Form Message (“Low Bat-MS2000”) ** 

1 Hour 

Summary of Contents for MS2000X Series

Page 1: ...ts including SuperCELL LTX200 and TPASS WorkForce and others The MS2000X has several enhanced features including a simple interface to existing security and alarm systems The MX2000X contains an optional audible horn and strobe light activated upon receiving emergency alarm signals from Grace worker safety devices ...

Page 2: ...ted by us ing a small screwdriver to depress the lever and then inserting the wire When the unit is plugged in to AC Power the Red Green AC Power Indicator glows or flashes Green indicating the system has AC Power and is ready for operation With loss of power the Red Green AC Power Indicator glows or flashes Red indicating the optional Backup Battery System has been automatically activated keeping...

Page 3: ...sting is complete the MS2000X is ready for use A Inputs and Power 1 15VDC In 2 12VDC Out 3 GND 4 GND 5 INPUT 1 6 Input Common 7 INPUT 2 8 Input Common 9 INPUT 3 10 Input Common 11 INPUT 4 12 Input Common B Power Terminals Line Neutral GND C Relay Terminals 4 Sets Numbered 1 4 Normally Open Common Normally Closed MS2000X Factory Default Relay Setting Relay Trigger Hold Activation Time 1 User Alarm ...

Page 4: ...ern 1 ON and 2 OFF Non Temporal 1 OFF and 2 OFF Temporal 1 ON and 2 ON March Time Tone 3 ON and 4 ON 2400 Hz 3 ON and 4 OFF Electromechanical 3 OFF and 4 OFF Chime 3 OFF and 4 ON Broadband Volume 5 ON and 6 ON High 5 ON and 6 OFF Mid 5 OFF and 6 OFF Low 7 ON and 8 ON Horn ON 7 OFF and 8 OFF Horn OFF ...

Page 5: ...r coverage of 200k Sq Feet and 1 mile outdoor clear line of site Indoor performance is subject to effects of building construction and RF noise 4 Opto Isolated 12VDC inputs See Page 3 for default configuration 4 Form C Relays See Page 3 for default configuration OPTION LIST CA AC powered models shipping to Canada require Canadian Electrical Inspection DC 12 15VDC model 0 5 Amps AC 110 220VAC 60Hz ...

Page 6: ...Pole Mounted with C Brackets MS2000X Side View MS2000X Side View Bolts and Bracket Assembly Pole Non Metallic MS2000X Top View Flat Washer Bracket Toothed Washer Pole Non Metallic Bolt Bracket Clamp Bolts and Bracket Assembly Improper Installation May Degrade Performance ...

Page 7: ... with optional 8 Pin Connector OPTIONAL 10 Foot Cable with Connector p n MS CA 10 CAUTION To avoid damaging mating pins carefully match up connector keyways when attaching phone dialer connector Wiring Pin 1 GREEN Normally Open PIn 2 WHITE Contact Com Pin 3 RED 12VDC Pin 4 Blue Input 1 Pin 5 ORANGE Normally Closed Pin 6 White Black Input Common Pin 7 BLACK GND Pin 8 Red Black Input 2 OPTIONAL 8 Pi...

Page 8: ... on how long an implied warranty lasts so the above limitations may not apply to you This warranty gives you specific legal rights and you may also have other rights which may vary from state to state Tech nical assistance is available by contacting Grace Industries Inc at 724 962 9231 Product issues may be reported at any time to Grace Industries Inc at 724 962 9231 FCC Statements Changes or modi...

Reviews: