Grace Engineered Products SAFESIDE R-3W2 Installation And Operating Instructions Manual Download Page 6

R-3W2

Page 4 of 12

<29

~

3           LINE-TO-LINE (VAC)

FLASHES / SEC (TYPICAL)

OR STORED ENERGY (VDC)

FLASHES/SEC (TYPICAL)

30

120

240

480

600

750

0

1.3

4.2

5.8

7.3

8.0

8.8

<27

30

48

110

300

600

1000

0

1.6

2.5

4.5

6.9

8.8

9.1

INDICATOR FLASH RATES (L1, L2, L3, GND)

5.

For Delta configured power, connect the 1 bar, 2 bar & 3 bar black wires to L1, L2, & L3
respectively (Fig. 1) on the fused or disconnect side of the 3-Phase line voltage. The
Green/Yellow stripe (Grn/Yel) wire

be connected to Earth Ground.  (Fig. 3)

6.

Wye configured power with grounded Neutral is connected the same as for Delta in step 5.
The Grn/Yel wire

connect to the neutral but to non-current carrying Earth

Ground.

The neutral will not be monitored for voltage by the Detector, only Phase-to-Phase

and Phase-to-Ground voltage will be detected. To include neutral monitoring go to step 7.

7.

Ungrounded or high resistance Wye configured power requires (2) additional units to include
all possible voltages the Neutral line introduces. Wire as shown in Figure 2.

8.

First disconnect all equipment that may introduce a hazard and

notify personnel before powering the panel!

With normal voltage applied, the L1, L2, and L3 indicator pairs

will flash at rates according to the applied voltage (See table below).

MUST

DOES NOT

Verifying Proper Operation:

Caution:

(a) TURN POWER ON.

Summary of Contents for SAFESIDE R-3W2

Page 1: ...ING INSTRUCTIONS R 3W2 www graceport com For technical questions contact Grace Engineered Products Inc 5001 Tremont Ave Davenport IA 52807 800 280 9517 563 386 9639 Fax UL APPROVED FOR CLASS I DIVISIO...

Page 2: ...l Atmospheric Conditions a 25 C to 40 C ambient b 21 Max Oxygen concentration per volume c barometric pressure range of 80 kPa 0 8 bar to 110 kPa 1 1 bar AUXILIARY DEVICE SUITABLE FOR USE IN CLASS I D...

Page 3: ...tures Operate 20 C to 55 C Code T5 Storage 45 C to 85 C Terminations 4 8 ft 18 AWG 90 C 1000V UL 1452 PVC insulation w nylon jacket L1 L3 Black w bar identification Fig 1 GND Green w Yellow stripe Hou...

Page 4: ...nect and within wiring distance to incoming Main Lines and Earth Ground Verify there is no interference with the free operation of the ON OFF disconnect mechanism 4 a For refer to knock out pattern be...

Page 5: ...R 3W2 Page 6 of 12...

Page 6: ...for Delta in step 5 The Grn Yel wire connect to the neutral but to non current carrying Earth Ground The neutral will not be monitored for voltage by the Detector only Phase to Phase and Phase to Grou...

Page 7: ...R 3W2 Page 7 of 12...

Page 8: ...to flash To verify operation of the GND indicators a normally closed push button switch could be placed in series with the L1 L2 or L2 lines Depressing the switch would simulate a phase loss enabling...

Page 9: ...R 3W2 Page 8 of 12...

Page 10: ...R 3W2 Page 9 of 12 Standard Mount Bezel Mount R 3W2 R 3W2 BZL...

Page 11: ...OLTAGE IF FLASHING SAFETY PROCEDURES STILL APPLY TEST BEFORE TOUCHING DANGER Part R 3W NP F2 Part R 3W2 NP F2 E N G I N E E R E D PRODUCTS INC G R A C E WWW GRACE COM PORT VOLTAGE IF FLASHING SAFETY P...

Page 12: ...R 3W2 Page 11 of 12 Fig 2...

Page 13: ...R 3W2 Page 12 of 12 Fig 3 Fig 4...

Reviews: