The information provided in this manual is up to date at the time of printing. Any 
revisions  to  this  document  will  supersede  the  content  included.  For  the  latest 
applicable version of this manual, visit our website or utilize the QR code.

Wiring

1. GPS recommends the CI-2 be powered constantly and NOT switched with the system or blower.

2. The CI-2 requires a 24VAC or 12-36VDC source. Connect the power wires as follows:

Black = Neutral

Red = Line

Green = Dry Contacts / BAS Alarm

White = Dry Contacts / BAS Alarm

3. Wire in BAS terminals (optional). The CI-2 is equipped with a set of dry contacts that are normally open and

close when the CI-2 is on and has no faults. The contacts are rated up to 125VAC and 300mA.

4. GPS PS-2 (optional). For incoming voltages from 110-277VAC.

Cleaning Cycle

The CI-2 comes with a preset cleaning cycle designed to clean the brushes once every day.

Troubleshooting

1. Unit will not power up, LED not illuminated:

a. Confirm proper voltage is applied to the correct terminal(s).

b. Try disconnecting and re-applying the power source.

2. If the unit does not operate properly after verifying the above instructions please contact GPS for additional

assistance.

Once powered, the unit initiates an internal check of all systems. If the auto cleaning wiper blade is not in the 

“home” position, it will move to the home position in series with the airflow.

Operation

CAUTION! 

Never touch brushes while operating, shock may occur.

ATTENTION:

 Ne touchez jamais les brosses pendant le fonctionnement, un choc peut se produire.

Summary of Contents for CI-2

Page 1: ...Installation Operation Maintenance Manual NOTICE This product is to be used only as directed Read entire manual before use Do not use unless properly installed ...

Page 2: ......

Page 3: ...ended to 3 years at no additional cost Register your products at www gpsair com product registration or scan the QR code Location NOTE Device should be installed after any filtration in system WARNING Make sure power is disconnected to the HVAC equipment before installation NOTE Use temperature Maximum ambient temperature in which unit shall be used 140 F 60 C AVERTISSEMENT Assurez vous que l alime...

Page 4: ...n high vibration and on non ferrous surfaces see Figure 2 3 Airflow should be aligned with the indicator on the CI 2 see Figure 3 Installation Methods Improper Installation Methods Figure 3 Figure 1 Magnet located here Figure 2 Magnet Installation improper airflow direction airflow not interacting with emitters blocked airflow wet conditions Bracket Installation Airflow Airflow ...

Page 5: ...imum installation location is on the fan inlet Ceiling Cassette 1 Optimum installation location is on the fan inlet shroud 2 Ensure installation of device does not hinder or interfere with any covers on ceiling cassette ...

Page 6: ...are the most likely installation locations 3 Ensure installation of the CI 2 does not hinder covers and guards PTAC 1 PTAC units are compact by design and configurations will vary greatly between manufacturers 2 The blower outlet and coils are the most likely locations 3 Ensure installation of the CI 2 does not hinder covers and guards ...

Page 7: ...e contacts are rated up to 125VAC and 300mA 4 GPS PS 2 optional For incoming voltages from 110 277VAC Cleaning Cycle The CI 2 comes with a preset cleaning cycle designed to clean the brushes once every day Troubleshooting 1 Unit will not power up LED not illuminated a Confirm proper voltage is applied to the correct terminal s b Try disconnecting and re applying the power source 2 If the unit does ...

Page 8: ...Charlotte NC 28208 980 279 5622 2022 GPS Air 2022 GPS Air GPS Air is the owner of certain trademarks that appear in our materials Please visit www gpsair com trademarks for a list of our marks www gpsair com GPS 041 28 R20 CI2 IOM ...

Reviews: