Operating Manual HG G-98830YA | English, Revision 02 | Date: 21.06.2021
54
Chapter 10 – Configuration of the System via the Service Interface
Additionally you can define the acknowledgement delay time
for procedure
3964R (see „Setting the acknowledgment delay time“ on page 55).
Setting the byte order
Use the parameter
(O)rder of Data Transfer
to select whether the highest byte should
be output first or last.
If you connect a Siemens PLC, this parameter has to be set to 0 (HiByte first)
Selection:
0 = HiByte first
1 = LowByte first
For setting the byte order:
Press the key
and enter the desired value.
Setting the content of the output telegram
With the parameter
(T)elegram Content Mask
you can define the desired compo
-
nents of your telegram by hexadecimal addition. The sequence of the parameters
cannot be influenced. It always corresponds to the sequence in Table 8 on page 36.
Value range:
0 … 1FFF (see column
Value
The length of the telegram will be adjusted automatically.
In order to specify the components of your telegram:
Press the key
and enter the desired value.
Example
You only want to output the
start character
, the
lateral deviation Y
, the
Code
and the
system status
. In accordance with the table, add the values 0x0000.0001,
0x0000.0002, 0x0000.0008 and 0x0000.01000, resulting in 0x0000.100B. This
means you have to enter 0x100b for the “(
)elegram Content Mask”.
Checking the generated telegram
With the parameter
(D)isplay Telegram Content
you can call up the generated tele
-
gram (see Figure 25). In the example the mask has the value 0x1fff and the telegram
length is 23.
Selection:
none, display function only
To display the generated telegram:
Press the key
.
The following screen appears: